Camus Hydronics DynaMax DMH201 Installation And Service Manual page 35

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

4) Select DHW Config
Inlet Sensor operation
5) Select Demand switch = Sensor only, and Press
6) Select Mod sensor = Inlet, and Press
DHW Stat operation
5) Select Demand switch = DHW switch, and Press
6) Select Mod sensor = Inlet, and Press
DHW Sensor operation
5) Select Demand switch = Sensor only, and Press
6) Select Mod sensor = DHW, and Press
7) Select DHW Setpoint, and enter desired setpoint using 5-way control
8) Place right hand toggle switch setting to REMOTE for remote operation (if
required)
,
go to step 7
,
go to step 7
31