Camus Hydronics DynaMax DMH201 Installation And Service Manual page 39

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Outdoor Sensor connected to Slave boiler 2 (DRH ONLY)
Description
Slave boiler outdoor sensor
configuration
When done correctly, the outdoor
temperature will be shown on the
Master boiler
Base load rate adjustment
Electrical Connection(s)
Slave Boiler
Master Boiler
Programming Instructions
1)
Place both toggle switches in LOCAL
2)
Press
and select Login
3)
Select Advanced Setup
4)
Select Sensor Configuration
5)
Select Outdoor temp src and Press
6)
Select S5 and Press
7)
Place both toggle switches in LOCAL
8)
Press
and select Login
9)
Select Advanced Setup
10) Select Lead Lag Config
11) Select Lead Lag Outdoor Reset
12) Select Outdoor reset enable = Enable and press
13) Set Max outdoor temp (Warm weather shutdown, WWSD)
14) Set Min outdoor temp (Outdoor Design)
15) Set Low Water Temp (Min. Water Temp.)
16) Set Outdoor boost maximum off point (Design Max.)
17) Select CH Config
18) Select Warm weather shutdown
19) Select Warm weather shutdown = Shutdown after demand has ended and press
20) Select Warm weather shdn setpoint