Camus Hydronics DynaMax DMH201 Installation And Service Manual page 33

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Modulation: System Sensor, Outdoor Reset Operation (Standalone)
NOTE: Outdoor Reset Module (PN: W8735S1000) required.
Description
Boiler operates with variable
setpoint determind by
outdoor reset curve
Modulates on system sensor
Heat demand is generated
when Remote Operator is
closed.
Electrical Connection(s)
Programming Instructions
1) Connect Remote Operator
2) Connect System sensor to System/Outdoor contacts
3) Connect Outdoor Sensor to J3 ECOM connector
4) Place both toggle switches in LOCAL
5) Press
and select Login
6)
Select Advanced Setup
7) Select CH Config
8) Select Outdoor Reset Config
9) Select Outdoor Reset and Press
10) Set Max outdoor temp (Warm Weather shutdown, WWSD)
11) Set Min outdoor temp (Outdoor Design)
12) Set Low Water temp (Min. Water Temp.)
13) Set Outdoor boost max off point (Design Max.)
14) Select Sensor Configuration
15) Select Outdoor temp src and Press
16) Select EnviraCOM and Press
17) Select Select CH Config (twice)
18) Select Modulation sensor = S5
19) Place right hand toggle switch to REMOTE for remote operation (if
required)
and select Enable
29