Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone)
Description
•
Boiler operates with variable
setpoint determind by
outdoor reset curve
•
Modulates on inlet sensor
(default)
•
Heat demand is generated
when Remote Operator is
closed.
Electrical Connection(s)
Programming Instructions
1) Place both toggle switches to LOCAL
2) Press
and select Login
3)
Select Advanced Setup
4) Select CH Config
5) Select Outdoor Reset Config
6) Select Outdoor Reset and Press
7) Set Max outdoor temp (Warm weather shutdown, WWSD)
8) Set Min outdoor temp (Outdoor Design)
9) Set Low Water temp (Min. Water Temp.)
10) Set Outdoor boost max off point (Design Max.)
11) Select Sensor Configuration
12) Select Outdoor temp src and Press
13) Select S5 and Press
14) Place right hand toggle switch to REMOTE for remote operation (if
required)
and select Enable