Camus Hydronics DynaMax DMH201 Installation And Service Manual page 24

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Table 11: Flow and Pressure Drop at a Given
Temperature Rise (Hydronic Heating)
30 °F (16.7 °C)
Input,
Temp Rise
Btu/Hr
USGPM
P Ft.
(min.
flow)
199,000
12.6
250,000
15.8
11.5
299,000
18.9
399,000
25.2
500,000
31.5
600,000
38.8
17.5
700,000
45.3
18.2
800,000
51.8
23.5
35 °F (19.4 °C)
Temp Rise
USGPM.
P Ft.
(min.
flow)
7.2
10.8
5.8
13.5
8.7
9.3
16.2
7.0
8.4
21.6
6.3
9.2
27.0
6.9
32.0
11.8
40.0
14.4
43.0
16.0
Table 12: Flow and Pressure Drop at a Given
Temperature Rise (DHW)
20 °F (11.1 °C)
Input,
Temp Rise
Btu/Hr
USGPM
(min.
flow)
199,000
19.2
250,000
23.5
299,000
28.8
399,000
38.4
500,000
48.6
600,000
57.6
700,000
70.4
800,000
77.6
P Ft.
25.9
28.3
25.8
23.9
29.4
34.2
40.0
43.2
20

Advertisement