Camus Hydronics DynaMax DMH201 Installation And Service Manual page 49

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Manual Reset Codes*
#
0
None
1-31
Internal hardware error
47
Flame rod to ground leakage
49
24VAC low/high
64
Fan speed not proved, ignition failure
67
Blocked flue condition
79
Heater Outlet high limit tripped
Stack limit tripped (PVC: 149
82
o
PPE: 230
F, SS, AL29-4C: 250
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
105
Flame detected out of sequence
Flame lost in Main Flame Establishing Period
106
(MFEP)
107
Flame lost early in run
108
Flame lost in run
109
Ignition failed
112
Pilot test flame timeout
113
Flame circuit timeout
149
Flame detected
* To eliminate the hard lockout error,
1)
Press the
button to clear the error on screen
Description
o
o
F, CPVC: 194
o
F)
#
0
None
29
Burner switch turned OFF
30
Burner switch turned ON
47
Flame rod to ground leakage
49
Abnormal 24Vac voltage
F,
50
Modulation Fault
61
Anti-short Cycle
62
Fan speed not proved
67
Interlock Off, safety circuit is open
69
Pilot test hold
78
Demand lost in run
79
Outlet high limit tripped (internal limit)
81
Delta-T limit exceeded (30
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
97-
Internal Fault
99
128
Fan speed failed during prepurge
129
Fan speed failed during preignition
130
Fan speed failed during ignition
131
Fan movement detected during standby
132
Fan speed failed during run
137
Interlock failed to close, safety circuit is open
110
Ignition failure occurred
111
Flame current below threshold (0.8Vdc)
149
Flame detected
150,
Flame not detected
291
301
Interlock Off, safety circuit is open
-
309
460
Interlock off during burn, safety circuit is open
Lead boiler was rotated based on measured run
614
time
Automatic Reset Codes
Description
o
F)
41

Advertisement

Table of Contents
loading

Table of Contents