Camus Hydronics DynaMax DMH201 Installation And Service Manual page 29

Gas fired residential commercial stainless steel boilers
Table of Contents

Advertisement

Levels of Access
Two levels of access to simplify the use of the boiler.
User – Access to general boiler and display settings and
adjustments to the central heating, domestic hot water and
lead lag setpoint.
Installer – Access to all user parameters and allows for
changes to additional boiler parameters to allow for ease of
startup and serviceability.
The screenshot below displays the default homescreen.
Figure 24: Home Screen
The first five parameters can be user customizable to reflect
the most vital information required on the boiler. The list of
available parameters is outlined in the table below. This can
be done by pressing:
1)
2)
Scroll to Display Setup, press
3)
Select the line item that is required to be altered,
press
4)
Select parameter, and press
PARAMETER
Standard parameters
System setpoint
Indicates active setpoint
Indicates temperature at modulation sensor
Operating temp
(Default: inlet sensor)
Outlet
Outlet Water Temperature [
Inlet
Inlet Water Temperature [
Outdoor
Outdoor Temperature [
Additional user configurable parameters
Outlet and Inlet water temperature differential
Delta T
o
[
F]
LL Operating
Indicates temperature at modulation sensor, if
Temp
equipped (Default: S5: system sensor)
LL system
Indicates active lead lag setpoint
setpoint
Fan speed
Actual fan speed [RPM]
Flame signal
Actual flame signal [Vdc]
Firing Rate
Target fan speed [RPM]
DHW
DHW Temperature [
DESCRIPTION
o
F]
o
F]
o
F], if equipped
o
F] ], if equipped
Stack
Stack Temperature [
4-20mA
4-20mA input, if equipped
PARAMETER
Boiler name
DynaMax HS model
State
Indicates current boiler operation sequence
Indicates origin of call for heat (CH, DHW,
Demand
Lead Lag)
Access Status
User, Installer
Outdoor
Outdoor Temperature [
Alert or Lockout. Section 5.4 provides
Error
additional details.
Pressing
provides additional troubleshooting information
on the diagnostic screen.
Figure 25: Diagnostic Screen
PARAMETER
Boiler pump
Pump A
Auxiliary
Pump B. 3-way valve diverter operation
Pump
DHW Pump
Pump C. Additional contact rated for 1/6hp.
Sequence of Operation
Pump A is energized for any call for heat
Pump B is energized on CH
Pump C is energized on DHW
LCI:
Flow Switch (N/O)
LWCO (N/O, if equipped)
Front Thermal Fuse (N/C)
Rear Thermal Fuse (N/C)
Blocked Flue Switch (N/C)
Interlock:
High Limit (N/C)
o
F], if equipped
DESCRIPTION
o
F], if equipped
DESCRIPTION