Thermal Solutions APEX APX425C Installation, Operating And Service Instructions page 88

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

10
Operation
(continued)
3. System Parameters (continued)
Installer's Password
Allows for custom password to be set. Must be 9 characters or less. Only
allows adjustment of supervisor password (supervisor default: 76). Cannot
change factory password.
Must enter current installer password.
Must enter new password and press enter.
Must re-enter new password and press enter.
Can be reset to supervisor default 76 if accessed with the Factory
level password (86).
CH Frost Protection
Disable
Frost Protection is not used.
Enable
Boiler and system circulators start and boiler fires when low out
side air, supply and return temperatures are sensed as follows:
Device
Started
Outside Air < 0°F ° (-18°C)
Boiler Pump
or Supply Water < 45°F (7.2°C)
Boiler
Supply Water < 38°F (3.3°C)
CH Frost Protection Setpoint
Outdoor Temperature at which pump is started for frost protection.
Warm Weather Shutdown Enable/Disable
Disable
Warm Weather Shutdown (WWSD) is not used.
Enable
A central heat boiler start is prevented if the outside temperature
is greater than the WWSD setpoint. WWSD is initiated as soon
as outside air temperature is above WWSD Setpoint. The control
does not require call for heat to be satisfied before entering
WWSD. The boiler will still start in response to a Domestic Hot
Water call for heat.
Warm Weather Shutdown Setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to shut down the boiler
when enabled by the "WWSD Enable" parameter.
Auto Jump to Home Page
Enable
After 15 minutes of no use, the display will automatically return to
the Home Page.
Disable
Display will not change screens to Home Page after 15 minutes.
System Date
Date used by display Alarm History screen. A battery is provided to maintain
the system date and time while the display is powered down.
System Time
Time used by display Alarm History screen. A battery is provided to
maintain the system date and time while the display is powered down.
88
Parameter and Description
Start
Temperatures
Temperatures
Outside Air > 4°F (-16°C)
or Supply Water > 50°F (10°C)
Supply Water > 50°F (10°C)
APEX
Installation, Operating, & Service Instructions
Stop
Factory Setting
Range / Choices
9 Character
76
Maximum
Enable
Enable, Disable
-50 to 50 (ºF)
0°F (-18°C)
(-45.6 to 10.0°C)
Disable
Enable, Disable
70°F
20 to 100°F
(21.1°C)
(-6.7 to 37.8°C)
Enabled
Enable/Disable
xx/xx/xxxx
xx:xx:xx
106308-05 - 3/23
N/A
N/A