Thermal Solutions APEX APX425C Installation, Operating And Service Instructions page 108

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

10
Operation
(continued)
M. Energy Management System (EMS) Interface
The control system has a fully featured ability to interface with an Energy Management System (EMS). The
control system allows remote control and monitoring via RS485 Modbus or through direct wiring. The following
sections outline setup of the EMS interface and adjustable EMS interface parameters. Select Main Menu >> EMS
to access EMS parameters.
1. Setup
Complete steps shown in Table 10-25 to set up a multiple boiler system with EMS interface.
Table 10-25: Energy Management System Setup Procedure
Step
Description
See Figure 8-9. Use standard Ethernet type cables to make connection between boilers. Alternatively, terminal
Install Ethernet
screws A, B, and C labeled Boiler-to-Boiler may be used.
1
cables between
NOTE: The same Ethernet cable that connects the Boiler-To-Boiler Sequence Master also connects the EMS
boilers
Modbus signals.
Enable EMS
2
Select Main Menu >> EMS >> Modbus Setup >> EMS Enable/Disable >> Enable.
communication
Set unique
Modbus
3
addresses
The EMS Modbus address may be independent to the Boiler number or boiler address. Select Main Menu >>
"Comm HMI
EMS >> Modbus Setup >> EMS Modbus Parameters. Follow on screen instructions.
Station"
NOTE: Each boiler must have a unique Comm HMI Station address.
Adjust
Communication parameters are adjustable. Select Main Menu >> EMS >> Modbus Setup >> EMS Modbus
4
communication
Parameters. Follow on screen instructions.
parameters
NOTE: Baud Rate and Parity must match the EMS settings for communication to be established.
Confirm
The display provides a list of all EMS signals. Select Main Menu >> EMS >> Points List. Use the list to verify
5
communication
signals sent and received from the EMS.
2. Remote Demand Parameters
Select
to access the following parameters.
Modulation Source
The boiler can modulate (vary boiler heat input) based on local or remote (4-20 mA or Modbus)
signals. Modulation begins after the start sequence finishes and the boiler is released to modulate.
Modulation Source has the following selections:
Local
Local setpoint and control is used to create firing rate.
4-20mA Input wired to Remote 4-20 mA terminals is used as modulation rate.
Modbus Modbus signal is used as modulation rate.
Central Heat Setpoint Source & Lead Lag Setpoint Source
The setpoint may be based on local (customer entered value or outdoor reset) or remote (4-20mA or
Modbus) signals. Setpoint Source has the following selections:
Local
Local setpoint and control is used to create firing rate.
4-20mA Input wired to Remote 4-20 mA terminals is used as modulation rate.
Modbus Modbus signal is used as modulation rate.
CH Demand Switch
The Central Heat demand (Enable Disable) can be directly wired to the boiler or provided by the
Modbus interface. Ignored when boiler is controlled by sequencer.
Local
Enable Disable terminals provide demand.
Modbus Modbus signal provides demand.
LL Demand Switch
The Sequencer Master's demand (Enable Disable) can be directly wired to the boiler or provided by
the Modbus interface. Used only on Sequencer Master boiler.
Local
Enable Disable terminals provide demand
Modbus Modbus signal provides demand.
4-20 mA Water Temp
Sets the Central Heat Setpoint temperature corresponding to 4 mA.
20 mA Water Temp
Sets the Central Heat Setpoint temperature corresponding to 20 mA.
108
SEE MODBUS SETUP PARAMETERS BEFORE PROCEEDING
Program COM2 only
Parameter and Description
APEX
Installation, Operating, & Service Instructions
Comments
Factory
Setting
Local
Local
Local
Local
130°F
(54.4°C)
180°F
(82.2°C)
Range / Choices
Local,
4-20 mA,
Modbus
Local,
4-20 mA,
Modbus
Local,
Modbus
Local,
Modbus
50°F (10°C) -
Central Heat Setpoint
50°F (10°C) -
Central Heat Setpoint
106308-05 - 3/23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apex apx525cApex apx625cApex apx725cApex apx825c

Table of Contents