Thermal Solutions APEX APX425C Installation, Operating And Service Instructions page 130

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

12
Troubleshooting
Table 12-11: Outdoor Sensor
Temperature vs. Resistance,
10kOhm NTC, Beta = 3435K
Outdoor Temperature
°F
-20
-28.9
-10
-23.3
0
-17.8
10
-12.2
20
30
40
50
10.0
60
15.6
70
21.1
76
24.4
78
25.6
80
26.7
90
32.2
100
37.8
110
43.3
120
48.9
130
(continued)
Ohms of
Resistance
°C
106926
80485
61246
47092
-6.7
36519
-1.1
28558
4.4
22537
17926
14356
11578
10210
9795
9398
7672
6301
5203
4317
APEX
Installation, Operating, & Service Instructions
Table 12-12: Header Sensor
Temperature vs. Resistance,
10kOhm NTC, Beta = 3950K
Temperature
°F
32
50
68
77
86
104
122
140
158
176
194
212
100
248
120
Ohms of
Resistance
°C
0
32648
10
19898
20
12492
25
10000
30
8057
40
5327
50
3602
60
2488
70
1752
80
1256
90
916
697
386
106308-05 - 3/23