Thermal Solutions APEX APX425C Installation, Operating And Service Instructions page 80

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

10
Operation
(continued)
Figure 10-2: Limit String Status Screen Showing
Central Heat Demand
Table 10-4: Limit String
Limit String
Description
Type
STAT
Heat Demand
A1
Annunciator 1
Annunciator 2/
A2/LCI
Load Control
Input
ILK
Interlock
9. Central Heating System Frost Protection
When enabled, Frost Protection starts the
boiler and system pump and fires the boiler
when low outside air and low supply water
temperatures are sensed. The Control
provides the following control action when frost
protection is enabled:
Table 10-5: Frost Protection
Device
Start
Started
Temperatures
Boiler
Outside Air < 0°F ° (-18°C)
Pump
or Supply Water < 45°F (7.2°C)
Boiler
Supply Water < 38°F (3.3°C)
E. Touch Screen Display Navigation
1. HOME SCREEN is the default state for the display, shown in Figure 10-3. The home screen displays basic
operating information and provides access to other screens through icons at the top of the screen.
80
"ON" indicates heat demand and enables control to fire to maintain water temperature at setpoint.
• Heat demand may be received from "Enable/Disable" terminals for Central Heat Demand, "DHW Demand"
terminals for DHW Demand, the Sequencer Master, or EMS Modbus inputs.
• Heat Demand input "ON" initiates pump and combustion air damper outputs.
A1 is the air proving switch and must cycle "ON" and "OFF" at appropriate times in order for boiler to start.
• A1 must prove "OFF" before blower starts. A1 "ON" before blower starts causes manual reset hard lockout
after a delay.
• A1 must prove "ON" after blower starts and before trial for ignition. A1 "OFF" during this time causes
manual reset hard lockout after a delay.
A2 limits are upstream of and connected in series with LCI limits. LCI must prove "ON" for boiler to start.
Boiler will shut down if LCI is turned "OFF" during operation.
• Hold message shown when LCI limit is "OFF" and Heat Demand is "ON".
• LCI Hold will never cause a manual reset lockout.
• Boiler may be disabled remotely by wiring an enable contact to the LCI "External Limit" terminals.
ILK must prove "ON" for boiler to start. Boiler will shut down with manual reset hard lockout if ILK is turned
"OFF" during operation. ILK OFF Lockout closes the Lockout Alarm contacts.
or Supply Water > 50°F (10°C)
Supply Water > 50°F (10°C)
APEX
Installation, Operating, & Service Instructions
Figure 10-3: Home Screen
Action
FROST PROTECTION NOTE
The Control helps provide freeze protection for the boiler
water. Boiler flue gas condensate drain is not protected
from freezing. Since the Control only controls the system
and boiler circulators individual zones are not protected.
It is recommended that the boiler be installed in a location
that is not exposed to freezing temperatures.
Stop
Temperatures
Outside Air > 4°F (-16°C)
106308-05 - 3/23