Product Description, Specifications and Dimensional Data
Table 1-6: Ratings
Input (MBH)
Model
Number
Min.
APX425C
80
APX525C
100
APX625C
125
APX725C
145
APX825C
160
Ratings shown are for installations at sea level and elevations up to 2,000 ft. at minimum vent length. For elevations
above 2,000 ft., see Appendix A Instructions for High Altitude Installations above 2,000 ft.
Net AHRI Water Ratings based on allowance of 1.15. Consult manufacturer before selecting boiler for installations
1
having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,
etc.
2

Unpacking Boiler

NOTICE: Do not drop boiler.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container.
D. Remove boiler from cardboard positioning sleeve
on shipping skid.
E. Move boiler to its permanent location.
8
Apex Series Gas-Fired Boilers
Gross
Output
Max.
(MBH)
399
375
500
485
625
594
725
689
800
760
APEX
Installation, Operating, & Service Instructions
Net Ratings
Thermal
Water
(MBH)
Efficiency (%)
1
326
94.1
422
97.0
517
95.0
599
95.0
661
95.0
3

Pre-Installation and Boiler Mounting

!
Explosion Hazard. Asphyxiation Hazard.
Electrical Shock Hazard.
Installation of this boiler should be undertaken
only by trained and skilled personnel from
a qualified service agency. Follow these
instructions exactly.
Improper installation, adjustment, service, or
maintenance can cause property damage,
personal injury or death.
NOTICE: Due to the low water content of the
boiler, mis-sizing of the boiler with regard to the
heating system load will result in excessive boiler
cycling and accelerated component failure.
Thermal Solutions DOES NOT warrant failures
caused by mis-sized boiler applications. DO NOT
oversize the boiler to the system. Multiple boiler
installations greatly reduce the likelihood of boiler
oversizing.
(continued)
Combustion
Efficiency (%)
94.5
96.0
96.0
95.0
94.0
WARNING
106308-05 - 3/23