Condensate Disposal - Thermal Solutions APEX APX425C Installation, Operating And Service Instructions

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

5

Condensate Disposal

A. Condensate Trap and Drain Line
1. All condensate which forms in the boiler or
vent system collects in the sump under heat
exchanger and leaves the boiler through
factory installed condensate trap.
2. The trap allows condensate to drain from
sump while retaining flue gases in the boiler.
The trap has factory installed overflow switch,
which shuts down the boiler in the event the
drain line becomes obstructed, preventing
proper condensate removal. Refer to Section
11 "Service and Maintenance" for condensate
trap and condensate overflow switch removal
and replacement procedure, if required.
3. Note the following when disposing of the
condensate:
a. Condensate is slightly acidic, typical pH
around 3.5 - 4.5. Do not use metallic pipe or
fittings in the condensate drain line. Do not
route the drain line through areas that could
be damaged by leaking condensate.
b. Do not route or terminate the condensate
drain line in areas subject to freezing
temperatures.
c. If the point of condensate disposal is above
the trap, a condensate pump is required to
move the condensate to the drain. Select
a condensate pump approved for use with
condensing furnaces. If overflow from the
pump would result in property damage,
select a pump with an overflow switch. Wire
this switch in series with installer provided
external high limit, to shut off the boiler, and,
if desired, in series with installer-supplied
alarm, to trigger an alarm in the event of
overflow.
d. Do not attempt to substitute another trap for
one provided with the boiler.
e. In order for boiler to work properly, the boiler
must be leveled during installation.
4. The condensate trap connection is located
at boiler left side, below inlet and outlet water
pipe connections. Refer to Figures 1-3, 1-4, 1-5
and 5-2.
5. Condensate trap must be filled up with water,
prior to boiler start-up and before connecting
any condensate line to the boiler to ensure
combustion products cannot escape from
operating boiler. To fill the trap, inject water
in the amount of 1 cup (240 ml) through
condensate trap connection. Do not overfill the
trap.
106308-05 - 3/23
APEX
Installation, Operating, & Service Instructions
6. Install tee for condensate overflow and vent as
shown in Figure 5-2.
!
WARNING
Asphyxiation Hazard.
Failure to fill the condensate trap with water prior
to boiler start-up could cause flue gas to enter
the building, resulting in personal injury or death.
7. If any additional condensate drain line is
needed, construct the extension from PVC or
CPVC Schedule 40 pipe. The factory supplied
¾ in. x 5-5/8 in. long PVC coupling, located in
the miscellaneous parts carton, must be used
to connect drain line to the condensate trap.
Do not over tighten coupling compression nuts
when connecting drain line and condensate
trap.
8. Size condensate drain line, pump and
neutralizer (if using other than manufacturer
neutralizer kit) to accommodate maximum
condensate flow shown in Table 5-1 "Maximum
Condensate Flow".
Table 5-1: Maximum Condensate Flow
Boiler
*Maximum Condensate Flow,
Model
APX425C
APX525C
APX625C
APX725C
APX825C
*Assumes 100% of water in fuel condenses.
!
WARNING
Asphyxiation Hazard.
Failure to install the condensate drain in
accordance with the above instructions could
cause flue gas to enter the building, resulting in
personal injury or death.
NOTICE: Boiler condensate is corrosive. Route
condensate drain line in a manner such that
any condensate leakage will not cause property
damage.
Some jurisdictions may require that condensate
be neutralized prior to disposal.
Use materials approved by the authority having
jurisdiction.
GPH
4.5
5.6
7.0
8.1
9.0
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apex apx525cApex apx625cApex apx725cApex apx825c

Table of Contents