Thermal Solutions APEX APX425C Installation, Operating And Service Instructions page 75

Commercial, condensing, high efficiency, direct vent, gas-fired, water boiler
Table of Contents

Advertisement

9
System Start-up
Asphyxiation Hazard.
If the throttle is very far out of adjustment on the "rich" (counter-clockwise) side, the boiler burner may be
running at 0% excess air or even with air deficiency. Operating the boiler in this condition may cause property
damage, personal injury or death.
At 0% excess air the CO
0%) and CO air free level will be extremely high (well over 1,000 PPM).
If the burner operates with air deficiency, the following phenomena may be observed:
% CO
will actually drop (% O
2
% CO
will actually increase (% O
2
If the boiler appears to operate with air deficiency, shut down the boiler and follow instructions in Paragraph U
"Correcting Throttle Screws Mis-Adjustment. Then, use a combustion analyzer to verify and adjust O
and CO air free to values shown in Table 9-2 for natural gas or Table 9-3 for LP gas.
V. Controls Start-up Check List
Check field wiring and control parameters per below Table 9-9 and Table 9-10. The control is factory
programmed with default parameters. Review parameters and adjust as necessary to conform to specific site
requirements. From Home Screen, select ADJUST to access below listed parameters. Login as needed to make
changes. For detailed login instructions, refer to Section 10 "Operation", Paragraph J. Parameter Adjustment.
Table 9-9: Field Wiring Checklist
Step
Wiring Location
1
120V PCB
Low Voltage
2
Connections PCB
106308-05 - 3/23
(continued)
!
readings will be either 11.9% CO
2
will increase) as the throttle is turned counter-clockwise
2
will drop) as the throttle is turned clockwise
2
Parameter
120V Line
Is line voltage connected with overcurrent protection?
Boiler, System,
Confirm pumps are connected. If using room air for combustion,
and DHW Pumps
confirm combustion air damper is connected.
Is the space heating thermostat connected. Ensure thermostat is a
Enable/Disable
"dry", non-powered input.
DHW Demand
Is an indirect water heater (IWH) providing a heat demand?
Auto Reset
Are external limits used? If so, ensure jumper is removed and limits
and Man Reset
properly connected. Also check that external limits are closed and
External Limit
any manual reset devices are reset.
Lockout Alarm
Are alarm contacts connected?
EnviraCOM
Are any EnviraCOM devices used?
Outdoor Sensor
Is an outdoor sensor used? Refer to Steps 1 & 7 in Table 9-10.
Is a header sensor used? A header sensor is required for the
Header Sensor
master boiler in a multiple boiler installation. Refer to Step 8 in
Table 9-10 to activate this input.
For single boiler servicing indirect water heater (IWH), install DHW
DHW Sensor
sensor at boiler-side inlet to IWH. Refer to Step 6 in Table 9-10 to
activate this input.
Is a 4-20mA input required for: 1) modulation input from an
energy management system, or 2) Central Heat setpoint input from
Remote 4-20mA
external multiple boiler control? If yes, refer to Step 11 in Table
9-10.
Are multiple boilers connected? If yes, refer to Steps 8 & 9 in Table
Boiler-to-Boiler
9-10 to activate boiler-to-boiler communication.
Is the boiler connected to an energy management system? If yes,
EMS
refer to Step 10 in Table 9-10.
Flow Switch
Is flow switch installed in piping and plugged in?
LWCO
Is a 24V LWCO used? Check installation.
APEX
Installation, Operating, & Service Instructions
WARNING
for natural gas or 13.8% CO
2
Description
for LP gas (O
will be
2
2
(or CO
)
2
2
75