Appendix A
(continued)
Start-up Instructions for Natural Gas or LP
1. Confirm Apex boiler size, type and installed
altitude prior to startup.
2. APX425C or APX525C LP conversion only:
Adjust throttle screw to preliminary setting per
Table A-2.
3. Start boiler as described in boiler Installation
manual and lock boiler in high fire (See Section
9 "System Start-up"). If boiler does not light,
turn throttle screw in ¼ turn increments in a
counterclockwise direction until boiler fires. Do
not stop here, follow Steps 4-7.
4. Verify CO
is within range shown in Table A-4
2
and CO air free is less than 200 ppm. If CO
and CO air free are within these limits, move
to Step 6 and check fan speed at high fire
operation only.
5. If CO
is outside the window outlined in
2
Table A-4, adjust throttle screw such that the
CO
falls in this range while boiler is locked
2
manually in high fire. Turning throttle screw
counter-clockwise increases the CO
clockwise rotation leans the mixture, reducing
the CO
. Once CO
2
Table A-4, check CO air free again to ensure
it is below 200 ppm. If CO air free is above
200 ppm turn throttle screw clockwise in ¼
increments until CO air free is below 200
ppm, while ensuring CO
specified in Table A-4. If CO air free is still
above 200 ppm, reduce fan speed in 100 rpm
increments until CO air free is less than 200
ppm.
!
WARNING
Asphyxiation Hazard. Offset screw is adjusted
at the factory. DO NOT touch the offset screw if
measured low fire CO
Table A-4.
6. Lock boiler in low fire (see Section 9 "System
Start-up"). Verify CO
in Table A-4 and CO air free is less than 200
ppm.
7. If low CO
is too high, decrease CO
2
offset screw counter-clockwise in less than 1/8
turn increments and checking the CO
CO air free after each adjustment. If boiler
is equipped with 2 gas valves, offset screw
adjustments must be done to both gas valves
equally and simultaneously. See Figure A-3 for
location of offset screw. Verify CO air free is
less than 200 ppm.
106308-05 - 3/23
Instructions for High Altitude Installations Above 2,000 ft.
, while
2
is within the limits in
2
remains in the range
2
is within limits specified in
2
is within range shown
2
by turning
2
and
2
APEX
Installation, Operating, & Service Instructions
8. If low fire CO
turning offset screw clockwise in less than 1/8
turn increments and checking the CO
CO air free after each adjustment. If boiler
is equipped with 2 gas valves, offset screw
adjustments must be done to both gas valves
equally and simultaneously. See Figure A-3 for
location of offset screw. Verify CO air free is
less than 200 ppm.
9. Start boiler five times at the above settings
to ensure boiler lights off without delay and
without noise. Check CO
to ensure that the CO
specified in Table A-4 and CO air free is below
200 ppm. Be sure to replace the screw cap in
2
the vent adapter when combustion testing is
complete.
10. Verify that the gas inlet pressure is between
the following limits with all gas appliances
(including the converted boiler) both on and
off:
• Natural Gas: 4.0 - 14.0 inches w.c.
• LP Gas: 8.0 - 14.0 inches w.c.
If inlet pressure is not within limits, adjust
before performing high altitude setup
procedure.
11. Return boiler to automatic mode. From
Operation Screen, select Automatic/Manual
Firing Rate Control >> Automatic Modulation.
Select HOME to return boiler to home screen.
Table A-2: Approximate Clockwise Throttle Screw
Turns for LP Gas (Propane) Conversion
Boiler Model
APX425C
APX525C
APX625C
APX725C
APX825C
Figure A-3: Gas Valve Detail
is too low, increase CO
2
and CO air free
2
is within the range
2
Approximate Throttle Screw Turns
3
N/A - Factory LP Builds
by
2
and
2
151