Heater Maintenance; Control Board Maintenance - Salda RIS 700 H EKO 3.0 Mounting And Installation Instruction

Hide thumbs Also See for RIS 700 H EKO 3.0:
Table of Contents

Advertisement

CAUTION: the heat exchanger cannot be used when the filters are removed!
6.7.

HEATER MAINTENANCE

• In case manual protection is activated, check for a fault before pressing the RESET button. If the fault is identified after it has been rectified,
press the RESET button using a screwdriver or a similar object.
• Electrical heater does not require additional servicing. The filters must be replaced as described above.
• Heaters are equipped with 2 thermal protection devices: an automatic self-resetting protection device that is activated at +50 °C, and a manually
restored protection device that is activated at +100 °C.
• After activation
of the manually restored protection device, make sure
elements cool down and the fans
The failure can be identified by a qualified technician only.
• If necessary,
the
electric heater can be removed. Disconnect the electrical connector from the heater and remove the heater.
6.8.

CONTROL BOARD MAINTENANCE

• Disconnect product unit from electric power source.
• Unscrew the bolts on the control box.
• Remove the control box cover.
• Disconnect all cables, wires, and connectors from the control board and unscrew the control board mounting bolts.
• Remove
the
control board.
• To reassemble, follow all maintenance steps in reverse order. When re-connecting cables, wires, hoses and connectors, make sure to match
each wire, hose and connector to
RIS 700 H EKO 3.0 v2023.1
stop
completely.
After the failure is detected and rectified, press the RESET button before starting the unit.
the
corresponding connection terminal and connector.
that
the unit is disconnected from the power supply. Wait until all heating
EN |
15