Installation
March 2024
2.6.1 
Conduit installation
 CAUTION
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Ensure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections or the transmitter housing.
Recommended conduit connections are shown in
Figure 2-14: Conduit installation diagrams
A. Possible conduit line positions
B. Sealing compound
C. Conduit lines
2.6.2 
Wiring
 CAUTION
Do not connect the power signal wiring to the test terminals. Voltage may burn out the
reverse-polarity protection diode in the test connection.
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use
24 AWG or larger wire, and do not exceed 5000 feet (1500 meters).
26
Reference Manual
Figure
2-14.
Emerson.com/Rosemount
00809-0100-4101