Mounting requirements
Impulse piping configurations depend on specific measurement conditions. Refer to
Installation examples
Liquid flow measurement
Place taps to the side of the line to prevent sediment deposits on the process isolators.
Mount the transmitter beside or below the taps so gases vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
Gas flow measurement
Place taps in the top or side of the line.
Mount the transmitter beside or above the taps so to drain liquid into the process line.
Steam flow measurement
Place taps to the side of the line.
Mount the transmitter below the taps to ensure that impulse piping will remain filled
with condensate.
In steam service above 250 °F (121 °C), fill impulse lines with water to prevent steam
from contacting the transmitter directly and to ensure accurate measurement start-up.
Note
For steam or other elevated temperature services, it is important that temperatures at
the process connection do not exceed the transmitter's process temperature limits. See
Temperature Limits
Installation examples
Figure 2-7: Liquid service
A. Flow
Reference Manual
for examples of the following mounting configurations.
for details.