Drive Data - Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

Parameter List
12.3

Drive data

PNU
Parameter Name in OP1
*:conf-P
Description
P070
MLFB(6SE70..)
*
MLFB (order number) of basic unit
46Hex
For parameter values, see Section "Initialization"
Type=O2;
P071
Line volts
47Hex
Line supply voltage for AFE (r.m.s. of line-to-line voltage)
This parameter specifies the incoming AC supply voltage.
It is used to calculate the setpoint DC link voltage (P125) and
the thresholds for fault messages "Line supply overvoltage",
"Line supply undervoltage" (P074) and "DC link undervoltage".
Type=O2;
P072
AFE current(n)
48Hex
AFE rated output current
Type=O2;
P074
Undervoltage threshold
4AHex
Response threshold for shutdown on line undervoltage. The
line supply voltage (P071) is the reference quantity.
Note:
P155: Maximum power failure time
Type=O2;
P077
FactSettingType
*
Selective factory setting
This parameter can be changed in the "MLFB Input" state
4DHex
(P052). If no MLFB has yet been entered, the selected factory
setting type becomes effective immediately an MLFB number
is entered and "MLFB Input" deselected (P052=0).
It is possible to activate a specific factory setting by selecting
"Par. Reset" (P052 = 1 or P970 = 0). This action does not,
however, change the setting in P077.
Parameter values:
0: Current factory setting remains valid.
1: AFE with OP:
2: AFE cabinet unit with terminal strip:
This setting initializes the following parameters to values
other than zero:
P554, P566, P603
3: Current factory setting remains valid.
3: AFE cabinet unit with OP:
Type:O2;
P078
Line frequency
Frequency of incoming AC supply
4EHex
Type=O2;
P080
Line filter C/mF
Capacitance of the filter capacitors of one phase of the AFE
line filter in mF for a "star circuit configuration". If the line filter
50Hex
capacitors are connected in a "delta configuration", then 300%
of the value must be parameterized.
Type=O2;
12-6
PKW: 1HEX=1
PKW: 1HEX=1 V
PKW: 1HEX=0.1 A
PKW: 1HEX=1 %
⇒not currently implemented
⇒not currently implemented
PKW: 1HEX=1
PKW: 1HEX=1 Hz
PKW: 1HEX=0.001
Range
[Unit]
Value Texts
0 to 255
PZD Gr.: -
90 to 1320
[V]
PZD Gr.: 0
4.0 to 6540.0
[A]
PZD Gr.: 0
6 to 100
[%]
PZD Gr.: −
0 to 4
PZD Gr.: -
50 to 60
[Hz]
PZD Gr.: −
0.000 to 10.000 −
PZD Gr.: 0
6SE7087-6CX86-2BA1
Operating Instructions SIMOVERT MASTERDRIVES AFE
01.2004
# of Indices
read:
_/_
Factory
write:
_/_
Settings
3 /U BR
0
3 /U
2 / ABR
2 / A
2 /U ABR
4 /U
2 / BR
2 / BR
65
3 /U BR
0
3 /U
2 / ABR
50
2 / A
3 / BR
0.000
3 / BR
Siemens AG