Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual page 95

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

01.2004
PNU
Parameter Name in OP1
*:conf-P
Description
P569
Src Jog2 ON
*
Source for the Inching 2 setpoint (control word 1, bit 8)
239Hex
See Section "Control word" for details
Parameter values: 0:
Other values:
B/R parameter
Type=L2; PKW format(HEX)=param.value
P572
Src.regen.enable
*
Source for control command "Regenerative feedback enabled"
23CHex
(control word 1, bit 12)
Parameter values: 0:
Other values:
B/R parameter
Type=L2; PKW format(HEX)=param.value
P575
Src No Ext Fault1
*
Source for control command "External fault 1" (control word 1,
23FHex
bit 15)
An L signal causes the drive to shut down on faults.
Parameter values: 0:
Other values:
B/R parameter
Type=L2; PKW: PKW format(HEX)=param.value
P576
Src. ext. 24V ok
*
Source for the bit for monitoring the external 24 V power
240Hex
supply.
This bit is connected to digital input 4 on the CUSA at the
factory.
Parameter values: 0:
Other values:
B/R parameter
Type=L2;PKW format(HEX)=param.value
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
No inching
1:
Illegal setting
2001:
SST1, word 1, bit 8
See permissible settings in Section "Control
word"
(process data connections of control word)
Regenerative feedback disabled
1:
Regenerative feedback enabled
2001:
SST1, word 1, bit 8
See permissible settings in Section "Control
word"
(process data connections of control word)
Illegal setting
1:
No fault
1001:
CUSA digital input 1
See permissible settings in Section "Control
word"
(process data connections of control word)
Ext. 24V not o.k.
1:
Ext. 24V o.k.
1001:
CUSA digital input 1
See permissible settings in Section "Control
word"
(process data connections of control word)
Operating Instructions
Range
[Unit]
Value Texts
0 to 5001
PZD Gr.: 0
0 to 5001
PZD Gr.: 0
1 to 5001
PZD Gr.: 0
0 to 5001
PZD Gr.: 0
Parameter List
# of Indices
read:
_/_
Factory
write:
_/_
Settings
2
2 / BR
2 / BR
i001=0
i002=0
2
2 / BR
i001=1
2 / BR
i002=1
2
2 / BR
i001=1
2 / BR
i002=1
2
3 / BR
i001=1004
3 / BR
i002=1004
12-19