06.2005
No.
F025
UCE Ph. L1
A UCE shutdown has occurred in phase L1
F026
UCE Ph. L2
A UCE shutdown has occurred in phase L2
F027
UCE Ph. L3
A UCE shutdown has occurred in phase L3
F029
Meas. val. sensing
A fault has occurred in the measured value sensing
circuit.
• (r949 = 1) Offset cannot be adjusted in phase L1.
• (r949 = 2) Offset cannot be adjusted in phase L2.
• (r949 = 3) Offset cannot be adjusted in phases L1 and
L3.
F030
DC link short-circuit
A short-circuit in the DC link has been detected:
• (r949 = 1) During pre-charging of the DC link, a short-
circuit has been detected.
• (r949 = 2) A DC link short-circuit has been detected
during forming.
• (r949 = 3) A DC link short-circuit has been detected
during operation.
F035
Ext. fault 1
Parameterizable external fault input 1 has been activated
F036
Ext. fault 2
Parameterizable external fault input 2 has been activated
DC link ground fault
F039
An earth fault has been detected during DC-link
precharging
F040
AS internal
Incorrect operating status
F041
EEprom fault
A fault occurred as values were been saved to the
EEPROM
F042
Comp. time
Computation time problems
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
Description of fault
Operating Instructions
Fault messages
Check
• phase L1 for short circuit or earth fault
(-X2:U2 - including motor).
• the contacts on the CU.
Check
• phase L2 for short circuit or earth fault
(-X2:V2 - including motor).
• the contacts on the CU.
Check
• phase L3 for short circuit or earth fault
(-X2:W2 - including motor).
• the contacts on the CU.
Defect in the measured value sensing circuit
Defect in the power section (valve is not blocking)
Check the DC link
Check the load connected to the DC link
Check
• whether an external fault has occurred
• whether the lead to the appropriate digital input is
interrupted
• P575 Src No Ext Fault1
See section "Digital inputs" in Operator's Guide
Check
• whether an external fault has occurred
• whether the lead to the appropriate digital input is
interrupted
• P586 Src No Ext Fault2
See section "Digital inputs" in Operator's Guide
Check:
Maximum connected inverter power greater than
4 x AFE inverter power?
If No:
Check the DC link
If Yes:
Contact your local SIEMENS AG branch
Replace the CUSA (-A10) board
Replace the CUSA (-A10) board
Reduce the computation time load, increase P308
Sampling time,
check r725 Available computation time.
Faults and Alarms
Remedial measures
14-3