Afe Inverter - Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

06.2005
17.4

AFE inverter

EU low-voltage directive
73/23/EEC and RL93/68/EEC
EU directive EMC 89/336/EEC
EU machine directive 89/392/EEC
Approval
Type of cooling
Permissible ambient and cooling-
medium temperature
during operation
during storage
during transport
Installation height
Permissible humidity rating
Climatic class
Pollution degree
Overvoltage category
Degree of protection
Class of protection
Shock protection
Radio interference suppression
Standard
Options
Interference immunity
Paint finish
Mechanical specifications
Vibrations
During stationary use:
Constant amplitude
- of deflection
- of acceleration
During transport:
- of deflection
- of acceleration
Shocks
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
EN 50178
EN 61800-3
EN 60204-1
UL:
E 145 153
CSA:
LR 21 927
Air cooling with built-in fan
0° C to +40° C (32° F to 104° F)
(up to 50 °C, see Fig. "Derating curves")
-25° C to +70° C (-13° F to 158° F)
-25° C to +70° C (-13° F to 158° F)
≤ 1000 m above sea level (100 % load capability)
> 1000 m to 3500 m above sea level
(for load capability. see Fig. "Derating curves")
Relative humidity
Class 3K3 to DIN IEC 721-3-3 (during operation)
Pollution degree 2 to IEC 664-1 (DIN VDE 0110. Part 1).
Moisture condensation during operation is not permissible
Category III to IEC 664-1 (DIN VDE 0110, Part 2)
EN 60529
IP00
Class 1 to IEC 536 (DIN VDE 0106, Part 1)
to EN 60204-1 and DIN VDE 0106 Part 100 (BGV A2)
to EN 61800-3
No radio interference suppression
Radio interference suppression filter for Class A1 to EN 55011
Industrial to EN 61800-3
For interior installation
to DIN IEC 68-2-6
0.075 mm in the frequency range 10 Hz to 58 Hz
9.8 m/s² in the frequency range > 58 Hz to 500 Hz
3.5 mm in the frequency range 5 Hz to 9 Hz
9.8 m/s² in the frequency range > 9 Hz to 500 Hz
to DIN IEC 68-2-27 / 08.89
30 g, 16 ms half-sine shock
Table 17-7
AFE inverter, general data
Operating Instructions
≤ 95 %
during transport and storage
≤ 85 %
during operation (moisture
condensation not permissible)
Technical Data
17-7

Advertisement