Functions - Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

Parameter List
12.6

Functions

PNU
Parameter Name in OP1
*:conf-P
Description
P366
Auto Restart
Automatic restart (WEA) after power failure
16EHex
Parameter values:
0 =
Inhibited
1 =
Power failure acknowledgement only after power
recovery
2 =
AFE is restarted after power recovery
CAUTION:
External safety devices must be provided to
ensure that the AFE does not start accidentally
when P366 = 2!
RDS(2) parameter
Type=O2;
P387
Vd minimum
Response threshold for shutdown
183Hex
DC-link undervoltage in closed-loop current control mode
(P164 = 2). The line supply voltage is the reference quantity
(P071).
Type=O2;
P408
Forming time
DC link forming time
198Hex
This parameter defines the forming period for the DC link when
P052=20.
RDS parameter
Type=O2;
P409
Line contac. del.
Delay time for commencement of precharging process.
199Hex
This parameter can be used to implement a time-graded
sequence for starting up a number of drive units.
Type=O2;
12-14
PKW: 1HEX=1
PZD Gr.: -
PKW: 1HEX=1 %
PZD Gr.: −
PKW: 1HEX=0.1 min
PZD Gr.: 0
PKW: 1HEX=0.1 s
PZD Gr.: −
Range
[Unit]
Value Texts
0 to 2
5 to 140
[%]
1.0 to 600.0
[min]
0.0 to 6.5
[s]
6SE7087-6CX86-2BA1
Operating Instructions SIMOVERT MASTERDRIVES AFE
01.2004
# of Indices
read:
_/_
Factory
write:
_/_
Settings
2
3 / BR
i001=0
3 / BR
i002=0
3 / BR
100
3 / BR
2
2 / ABR
i001=10.0
2 / AB
i002=10.0
3 / BR
0.0
3 / B