Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual page 87

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

01.2004
PNU
Parameter Name in OP1
*:conf-P
Description
P155
max. t. pow.fail
Maximum time until the power failure fault (F009) or line supply
undervoltage fault (F004) is output.
9BHex
If the unsmoothed line supply voltage falls below the threshold
parameterized in P074, the inverter firing pulses are inhibited.
The main contactor remains closed. If the line supply voltage
does not increase above the minimum threshold (P074) within
the maximum time for a power failure, the power failure fault
F009 is output and the main contactor is opened (de-
energized).
If the smoothed line supply voltage falls below the threshold
parameterized in P074, fault message F004 "line supply
undervoltage" is output.
Type=O2;
PKW: 1HEX=1 s
P160
I start(mot,max)
Maximum current limit for motor operation.
A0Hex
The line current is limited by this parameter.
RDS(2) parameter
Type=I2;
PKW: 1HEX=0.1 %
P161
I start(gen,max)
Maximum regenerative current limit.
A1Hex
The regenerative feedback current is limited to the value set
here..0
RDS(2) parameter
Type=I2;
PKW: 1HEX=0.1 %
P164
Operating mode
Selection of the operating mode
A4Hex
Parameter values:
0: Operating mode "reactive power compensation"
The setpoint for the reactive power can be set via P122.
1: Operating mode "cos(PHI)"
The setpoint for the cos(PHI) can be set via P120.
2: Operating mode "closed-loop current control"
The source of the current setpoint must be entered via
P486.
3: Regenerative partial load
RDS(2) parameter
Type=O2;
PKW: 1HEX=1
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
ZD-Gr.: 0
PZD: 4000HEX = 400 %
PZD: 4000HEX = 400 %
PZD Gr.: −
Operating Instructions
Range
# of Indices
[Unit]
Factory
Value Texts
Settings
0 to 3000
[ms]
100
0.0 to 150.0
2
[%]
i001=150.0
i002=150.0
−150.0 to 0.0
2
[%]
i001=-150.0
i002=-150.0
0 to 2
2
i001=1
i002=1
Parameter List
read:
_/_
write:
_/_
3 / BR
3 / BR
3 / ABR
3 / A
3 / ABR
3 / A
3 / ABR
3 / A
12-11