Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual page 79

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

01.2004
PNU
Parameter Name in OP1
*:conf-P
Description
r012
Base/Reserve
Basic/reserve settings of the process data connections for
CHex
setpoints and control word bits
Parameter values:
0: Basic setting
1: Reserve setting
Analog output: 100 % with code number (PWE) = 16384
Type=O2;
r013
Operat. hours
Display of hours run with enabled inverter (in Run operating
state).
DHex
Indices:
i001 = Days: Days (0...9999)
i002 = Hrs.: Hours (0...24)
i003 = Sec.: Seconds (0...3600)
Type=O2;
r030
Line volts
Actual line voltage (fundamental r.m.s.)
1EHex
Analog output: 100 % with code number (PWE) = 4 * P071
Type=O2;
r032
Line frequency
Actual frequency of line voltage
20Hex
Analog output: 100 % with code number (PWE) = 163.84 Hz
Type=O2;
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
PKW: 1HEX=1
PZD Gr.: 0
PKW: 1HEX=1
PZD Gr.: 0
PKW: 1HEX=1 V
PZD Gr.: 7
PKW: 1HEX=0.01 Hz
PZD Gr.: 0
Operating Instructions
Range
# of Indices
[Unit]
Factory
Value Texts
Settings
Basic
Reserve
3
d
h
s
[V]
[Hz]
Parameter List
read:
_/_
write:
_/_
2 / BR
2 / BR
2 / BR
2 / BR
12-3

Advertisement

Table of Contents
loading