Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual page 164

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

Technical Data
NOTE
17-8
Permissible rated output voltage in %
acc. to VDE 0110 / IEC 664-1
(not necessary acc. to UL / CSA)
100
75
50
0
1000
2000
Installation altitude above sea level in m
Permissible rated current in %
100
75
50
25
0
0
10
20
30
Cooling-medium temp. in °C
Permissible rated current in %
100
90
80
70
60
0
1000
2000
Installation altitude above sea level in m
Fig. 17-3
Derating curves
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
→ Total derating = 0.845 x 1.125 = 0.95
3000
4000
40
50
3000
4000
x Derating
altitude
ambient temperature
6SE7087-6CX86-2BA1
Operating Instructions SIMOVERT MASTERDRIVES AFE
06.2005
Temp
Derating
[°C]
factor K
2
50
0.76
45
0.879
40
1.0
35
1.125 *
* See the
30
1.25 *
following
Note
1.375 *
25
Altitude
Derating
[m]
factor K
1
1000
1.0
2000
0.9
3000
0.845
4000
0.8
K
= 0.845
1
K
= 1.125
2