Installation
Water cooling
Built-in components
in the roof section
Implementation of
24 V DC auxiliary
supply
5-12
Inverters with water cooling (item number suffix: -1AA0) are suitable for
mounting in enclosed cabinets (IP54). The components not mounted on
the heat sink, such as the electronics and the DC link capacitors, are
cooled by heat transfer at the heat sink fins. To enable this heat
transfer to take place, air circulation inside the unit is necessary.
Therefore, when installing the chassis unit in a cabinet, you must make
sure that the air being discharged from the fan can flow into the inside
of the chassis. The partitions to be provided in units with air cooling
are a disturbing factor in this case! They should not be mounted.
For an application in the types of protection > IP40, a distance of at
least 90 mm must be observed between the top of the units and the top
of the cabinet.
The units do not require external cooling air.
Additional losses cannot be dissipated!
1-inch internal threads are envisaged for the water connection. The
connecting nipples should be made of stainless steel or thick-walled
aluminum. Ideally, the connection should have flat seals. If the
connecting pieces enclosed with the units are used, these should be
sealed with Loctite 542 or with teflon tape.
Cooling water infeed (blue) and return (red) must be connected
according to the color scheme! The color markings can be found next to
the 1-inch water connection below the heat sink.
If components are built into a cabinet roof section (DC bus, DC 24 V
supply), these should be placed in the center if possible so that the air
leaving the fans can reach the openings in the roof cover unobstructed.
In order to ensure fault-free operation of the equipment (in terms of
electromagnetic compatibility), it is advisable to provide each chassis
unit with its own 24 V DC auxiliary supply with isolating transformer.