(c) Time performance
The time from signal input to STO shuts off when deceleration fales with SS1 enabled is as follow.
T1: The time from signal input to SS1 activation including:
T1-1: SS1 reaction time: 7.1ms
T1-2: Input signal filter
DSI: DSI Filter Time (refer to (c) DSI filter configuration.)
External emergency stop input: 7.1ms
Emergency stop switch (Operation panel): 7.1ms
Emergency stop switch (T/B): 7.1ms
Door switch input: 32.1ms
Enabling device input: 32.1ms
Mode selector: 32.1ms
3-position enable switch: 32.1ms
T2: The time from SS1 activation to STO shuts off including:
T2-1: SS1 deceleration monitoring time
T2-2: STO reaction time:7.1ms
The time from signal input of robot controller to STO shuts off
= <T1-1> + <T1-2> + <T2-1> + <T2-2>
4 SAFETY MONITORING FUNCTIONS
Safety Monitoring Functions 4-65