Electrical installation
ATTENTION!
To ensure electromagnetic compatibility (EMC), a shielded Ethernet
cable must be used. Connect the cable shielding on both sides to
earth (i.e. on each of the connected devices).
The metal housing of the M12 circular plug-in connector is connected
to the actuator housing, which is why the functional earth must be
connected to earth on the actuator housing. Use a short line (max.
1 m) with a cross-section of at least 1.5 mm2 for connecting to earth.
For versions with Fieldbus gateway, the Fieldbus gateway must
also be connected to earth along with the actuator. This connection
to earth is made with the ground terminal supplied, to the circular
plug-in connector of the connected Ethernet cable.
FE functional
earth
Fieldbus gateway
Push-in connector
Pin
Pin assignment
1
Transmit +
2
Receive +
3
Transmit –
4
Receive –
Fig.21:
Electrical connection, pin assignment and FE functional earth at
fieldbus gateway
Female connector
M12, 4-pin
Ethernet, Port 1 and 2
3
4
2
1
FE functional earth
Actuator
AG2
Fig.22:
FE functional earth at actuator
8.3
Electrical installation with cable gland
(only AG2)
WARNING!
Risk of injury due to improper installation.
▶ Installation may be carried out by authorised technicians
only and with the appropriate tools.
▶ Observe general engineering standards & rules during
installation.
Risk of injury due to unintentional activation of the system
and uncontrolled restart.
▶ Secure the system against unintentional activation.
▶ Following installation, ensure a controlled restart.
NOTE!
To ensure electromagnetic compatibility (EMC) the functional
earth must be connected to earth with a short line (max. 1 m).
The functional earth must have a cross-section of at least 1.5
mm
.
2
English