Type 3360 and 3361
Installationofthevalve
Signal
Wire
Pin
Assignment
type*
color
Frequency
1 brown not used
- externally
2 white
PV1: clock input +
supplied
3 blue
not used
4 black
PV2: not used
5 gray
PV3: clock input –
Pt 100
1 brown not used
(see note
2 white
PV1: process actual 1
below)
(current feed)
3 blue
not used
4 black
PV2: process actual 2
(compensation)
5 gray
PV3: process actual 3
GND
* Can be adjusted by software:
Inputs / Outputs → PV → ANALOG.type
(signal source: PV.source → Analog).
Tab. 5:
X2 – M12 socket, 5-pole, input signals process actual value (only
available for devices with process controller function)
NOTE!
For reasons of wire resistance compensation, connect the
Pt 100 sensor via 3 wires. Always bridge Pin 4 and Pin 5 on
the sensor.
Connection lines may be a maximum of 20 m long.
When the operating voltage is applied make the required basic
settings and adjustments for the electromotive control valve. For a
description see chapter "9 Start-up".
8.2
On the
External
device
circuit
side
8.2.1 Safety instructions
2
Clock +
Risk of injury from improper installation.
5
Clock –
▶ Installation may be carried out by authorized technicians only
2
▶ Observe the general rules of technology during installation.
Pt 100
Risk of injury from unintentional activation of the system and
uncontrolled restart.
4
▶ Secure system against unintentional activation.
▶ Following installation, ensure a controlled restart.
5
NOTE!
To ensure electromagnetic compatibility (EMC) the functional
ground must be grounded with a short cable (max. 1m).
The functional ground must have a cross-section of 1.5 mm².
Electrical installation with cable
gland
WARNING!
and with the appropriate tools.
Using the set-point value input 4...20 mA
If several devices of Type 3360 or 3361 are connected in
series and the power supply to a device in this series con-
nection fails, the input of the failed device becomes highly
resistive. As a result, the 4...20 mA standard signal fails.
english
23