Baxi MK SYSTEM Installation, User And Service Manual page 47

Table of Contents

Advertisement

Parameters
Description of the parameters
Zone Function
Functionality of the zone
CP020
Postrun zone pump
Pump post runtime of the zone
CP040
Can be set from 0 Min to 20 Min
Room T holiday
Wished room zone temperature on holiday period
CP060
Can be set from 5 °C to 20 °C
MaxReducedRoomT.L
Max Room Temperature limit of the circuit in reduced mode, that allows
im
switching to comfort mode
CP070
Can be set from 5 °C to 30 °C
TypeReducedNightMo
Type of reduced night mode, stop or maintain heating of circuit
de
CP340
Heating is deactivated when the room temperature setpoint in the timer pro­
gramme is below the threshold set in CP070
User T.Room Activity
Desired room temperature setpoint for standby mode
CP080
Can be set from 5 °C to 30 °C
User T.Room Activity
Desired room temperature setpoint for Welcome mode
CP081
Can be set from 5 °C to 30 °C
User T.Room Activity
Desired room temperature setpoint for Absence mode
CP082
Can be set from 5 °C to 30 °C
User T.Room Activity
Desired room temperature setpoint for Morning mode
CP083
Can be set from 5 °C to 30 °C
User T.Room Activity
Desired room temperature setpoint for Evening mode
CP084
Can be set from 5 °C to 30 °C
User T.Room Activity
Desired room temperature setpoint for Custom mode
CP085
Can be set from 5 °C to 30 °C
Manu
Manually setting the room temperature setpoint of the zone
ZoneRoomTempSet
Can be set from 5 °C to 30 °C
CP200
CP210
Comfort footpoint of the temperature of heat curve of the circuit
Zone HCZP Comfort
Can be set from 15 °C to 90 °C
Zone HCZP Reduced
Reduced footpoint of the temperature of heat curve of the circuit
CP220
Can be set from 15 °C to 90 °C
Zone Heating Curve
Heating curve temperature gradient of the zone
CP230
Can be set from 0 to 4
ZoneRoomUnitInfl
Adjustment of the influence of the zone room unit
CP240
Can be set from 0 to 10
Floor cool setpoint
Cooling flow temperature setpoint for the underfloor cooling
CP270
Can be set from 11 °C to 23 °C
Fan cool setpoint
Cooling flow temperature setpoint for the fan convector
CP280
Can be set from 7 °C to 23 °C
OperatingZoneMode
Operating mode of the zone
CP320
Pump type
The connected pump type
CP450
7856310 - v02 - 21122023
Disable
Direct = radiators. Cooling not possible.
Mixing Circuit = underfloor heating for the CIRCA and CIRCB . Cooling
possible.
Swimming pool. = not used.
High Temperature = not used.
Fan Convector Cooling possible.
Stop heat demand
Continue heat demand
Scheduling
Manual
Off
On/Off
Modulating PWM
Modulating LIN
9 Parameters
Factory setting
CIRCA
Mixing Circuit
0 Min
6 °C
16 °C
Continue heat demand
16 °C
20 °C
6 °C
21 °C
22 °C
23 °C
20 °C
15 °C
15 °C
1.5
3
18 °C
7 °C
Scheduling
Modulating PWM
47