Configuring Sources Of Energy; Configuring The Electrical Energy Consumption Function - Baxi MK SYSTEM Installation, User And Service Manual

Table of Contents

Advertisement

8 Settings
Parameter
Multifunct output
HP188
8.16

Configuring sources of energy

8.16.1

Configuring the electrical energy consumption function

Tab.24
Access path
> Heat Pump >
23.5
Parameters, counters,
signals > Settings
38
Description
Configure the function of the multifunctional
output
Cooling mode
Defrosting mode
Silent Mode
On
Parameter
Description
HP energy consumpt
Method selection to calculate the
HP157
electrical consumption of the heat
pump
Elec pulse value
Pulse value from the electricity me­
HP033
ter
2. Configure the following parameter:
Adjustment required
Configure the parameter based on the required
status information.
In order for the energy metering to work, adjust the parameter: Value of
the pulse coming from the electrical counter connected to the energy
meter.
1. Note the energy meter pulse value according to standard EN
62053-31.
2. Configure the following parameters:
Tab.25
Parameter value based on the type of energy meter
Number of pulses per
kWh
1000
500
250
200
125
100
50
40
25
20
10
8
5
4
2
1
The electricity readings are displayed on the meters CH consumed
(AC005), DHW consumed (AC006) and Cooling consumed
(AC007).
Adjustment required
Measured: the consumption for the
outdoor unit is measured by the en­
ergy meter and the consumption for
the indoor unit and the heating ele­
ment is estimated.
The adjustment depends on the type
of energy meter installed.
Adjustment range: 0 (no metering) to
1000 Wh.
Default value: 1 Wh
Values to be configured for the Elec pulse
value (HP033) parameter
1
2
4
5
8
10
20
25
40
50
100
125
200
250
500
1000