Tab.21
Improving heating comfort
Access path
> DHW tank >
Parameters, counters,
signals > Settings
8.14

Reducing the noise level of the outdoor unit

Tab.22
Access path
Parameter
HP silent mode
HP058
Heat Pump >
23.5
Parameters,
counters, signals >
Settings
Tab.23
Access path
Parameter
Low noise start
time
Heat Pump >
23.5
HP094
Parameters,
counters, signals >
Low noise end
Settings
time
HP095
8.15

Configuring the multifunctional output

Access path
>
Installer > Installation setup > Heat Pump > Advanced
7856310 - v02 - 21122023
Parameter
Description
Max DHW duration
Maximum duration of the domestic
DP047
hot water production.
Min CH before DHW
Minimum heating duration between
DP048
two periods of domestic hot water
production.
Hysteresis DHW
Hysteresis temperature relative to
DP120
the DHW temperature setpoint
On
Description
Heat pump silent mode level
No silent mode : normal operation
Silent mode level 1 : level 1 sound reduction
Silent mode level 2 : level 2 sound reduction, which is
higher than level 1
On
Description
Start time of the heat pump low noise function
End time of the heat pump low noise function
3. Check the improvement in comfort over one week.
4. Readjust the parameters as needed.
Silent mode is used to reduce the noise level of the outdoor unit during
specified programmed hours. This mode limits the performance of the heat
pump.
1. Activate silent mode.
2. Program the operating range in silent mode.
The multifunctional output X19 for the EHC-14 PCB sends an on/off signal
(dry contact) based on the status of the Cooling mode, Defrosting mode or
Silent Mode.
1. Follow the access path described below.
Adjustment required
Reduce the maximum authorised
duration for domestic hot water pro­
duction.
Shorter period of hot water produc­
tion.
Increase the minimum heating dura­
tion between two domestic hot water
production runs.
The time between two periods of hot
water production is increased.
Increase the setpoint temperature
differential triggering the domestic
hot water tank to be charged.
Less frequent period of hot water
production.
Adjustment required
Silent mode level 1
or
Silent mode level 2
Adjustment required
22:00
06:00
8 Settings
37