4. How to Use Test Mode

Test Menu 4: Analog Output Test

In the test mode, the following operation is available.
When ME-4210-SS96B (optional plug-in module) is not installed, this menu is not displayed.
Test Menu
DISPLAY
SET
①Analog output
CH1 test
DISPLAY
SET
②Analog output
CH2 to 4 test
SET
Test Menu
Set the test menu number to 4.
*Refer to the right figure.
The test operation will be executed for analog output CH1.
Input is not necessary.
Output
0%
25%
0%
50%
25%
75%
50%
100%
75%
100%
Note: The output item selected at Setting menu 6: Analog output settings is displayed.
The test operation will be executed for analog output CH2.
The test method is the same as ①Analog output CH1 test.
<To shift to other test menu>
⇒ Select other test menu number and then press
<To end the test mode>
Select End in the test menu number and then press
. The screen
will return to the operating mode.
SET
Output
specifications
4 to 20 mA
4 mA
1st line: Analog output CH1
3rd line: Percentage value in the output
8 mA
4th line: The selected output item and a
12 mA
16 mA
20 mA
64
measured value corresponding
to the percentage value in the
output
.
SET
.