Features
The instrument measures load status by wiring the secondary sides of VT (Voltage Transformer) and CT
(Current Transformer) in the power receiving and distribution system and displays various measured values.
The instrument supports Active Energy Class 0.5S and harmonic measurement (1st to 19th).
Active energy can be measured by dividing into three time periods such as peak, off-peak, and shoulder.
(Periodic Active Energy)
This instrument enables measurement of active energy/reactive energy/ apparent energy for any period
(interval). (Rolling demand active power/Rolling demand reactive power/Rolling demand apparent power)
The password protection prevents undesired setting change and measured data deletion.
The transmission function (MODBUS RTU communication, CC-Link communication, or MODBUS TCP
commination) transmits measured data to superior monitoring systems.
*CC-Link communication is available when ME-0040C-SS96 (optional plug-in module) is installed.
*MODBUS TCP commination is available when ME-0040C-SS96 (optional plug-in module) is installed.
The logging function enables to back up measured values in a SD memory card even when a MODBUS RTU
communication error occurs.
*It is available when ME-0000BU-SS96 or ME-0000BU25-SS96 (optional plug-in module) is installed.
This instrument itself can output key measuring elements such as current, voltage, active power, power
factor, and active energy at the power receiving point by installing an optional plug-in module with analog
output/pulse output function. It is ideal for remote monitoring.
*It is available when ME-4210-SS96B (optional plug-in module) is installed
The built-in logging function provides the logging of measured values, alarm logs, and system logs into this
instrument.
The standard complies with the requirements of CE marking, UL standards, KC mark, and FCC/IC.
The support function for checking input wiring enables to determine the wiring condition in the test mode.
When either a voltage input or current input are incorrectly wired, the incorrect wiring part is displayed on the
screen and it also shows a current phase angle, a voltage phase angle, and each value of active power,
voltage, and current.
Trademark
MODBUS is a trademark of Schneider Electric USA Inc.
Ethernet is a trademark of FUJIFILM Business Innovation Corp.
SD Logo, SDHC logo are trademarks of SD-3C, LLC.
Other company and product names herein are trademarks or registered trademarks of their respective owners.
In the text, trademark symbols such as 'TM' and '®' may not be written.
2