Run Time Options - Honeywell Vertex M User Manual

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

5.6.1 Run Time Options

Use the Run Time Options Window to perform one of the following four functions:
Start or stop an analyzer from monitoring
l
Enable or temporarily disable a point
l
Enable or temporarily disable an alarm
l
Enter a comment event into the event list
l
A point or alarm disabled in the Run Time Options window will remain disabled until it is again
enabled in this window or analyzers are power cycled. However, an event window will open to
remind operators the alarm or point is no longer providing coverage. The event will occur after
the timeout period set in the configuration window.
Vertex M always displays the following items in the Run Time Options window.
To Start or Stop an Analyzer from Monitoring
Stopping an analyzer from monitoring prevents the system from triggering false alarms during
testing and maintenance.
1. Choose Monitoring from the function buttons at the bottom of the screen.
2. Select the analyzer(s) from the keypad. The selected analyzer(s) will turn dark gray on the
keypad.
3. Choose Stop or Start Monitor to change the state of the analyzer.
The status indicator changes to reflect the current status on the main screen, and on the
analyzer button on the keypad.
Vertex M
101
User Manual