8.10 Series 3 Rack 4-20mA Analog Output Option

8.10.1 Overview

The application provides an isolated analog output option for the Series 3 Vertex M by utilizing
an Ethernet adaptor and signal conditioner/isolator module. The analog output option
communicates with the PLC processor module via the Ethernet adaptor.

8.10.2 Electrical Isolation

The Allen Bradley 5069-OF8 analog output provides sourcing milliampere signals. These are
isolated from the Vertex M rack but not from each other. This is shown in the following image.

8.10.3 Hardware Requirements

Series 3 Vertex M supports the isolated 4-20mA output using 5069-OF8 analog output
modules.
Analog Output Option Parts
Vertex M
RJ45 Ethernet Cable
5069-AENTR Ethernet IP Adaptor
5069-OF8 Analog Output Modules (Qty 3)