Industrial Electronic Devices
ETHERNET PROTOCOL:
The communiocation is made through UDP frames.
The frame that the HD67576 sends is composed like follow:
(DLR + 7) ÷ (DLR + CLP + 6)
(DLR + CLP + 8) ÷ (DLR + CLP + DLW + 7)
DLR + CLP + DLW + 8
DLR + CLP + DLW + 9
If the "DLR" and/or "DLW" has got the value 0x00 there are no data to read/write.
The "Data OUT" are the same that the HD67576-A1 receives with the frame sended by the companion.
The frame that the HD67576 expects is composed like the follow:
(DLR + 7) ÷ (DLR + CLP + 6)
(DLR + CLP + 8) ÷ (DLR + CLP + DLW + 7)
DLR + CLP + DLW + 8
(DLR + CLP + DLW + 9) ÷ (DLR + CLP + DLW + CLD + 8)
DLR + CLP + DLW + CLD + 9
ADFweb.com Srl – IT31010 – Mareno – Treviso
Byte Number
1
2
3
4
5
6 ÷ (DLR + 5)
DLR + 6
DLR + CLP + 7
Byte Number
1
2
3
4
5
6 ÷ (DLR + 5)
DLR + 6
DLR + CLP + 7
User Manual PROFIBUS Slave / Ethernet - Converter
Document code: MN67576_ENG
Description
Address PROFIBUS HD67576 + 0x80
Address PROFIBUS Slave simulated
Writing state (must be at 0)
Slave informations
Data length (OUT Slave)
Data OUT
Configuration length (programmed)
Configuration programmed
Data length (IN Slave)
Data IN
Fixed at 0
Fixed at 0
Description
Address PROFIBUS + 0x80
Address PROFIBUS Slave simulated
Writing state (must be at 0)
Slave informations
Data length (OUT Slave)
Data OUT
Configuration length (programmed)
Configuration programmed
Data length (IN Slave)
Data IN
Configuration length ( of device)
Configuration of device
Fixed at 0
INFO:
www.adfweb.com
Revision 2.002
Page 25 of 29
Abbreviation
/
/
/
/
DLR
/
CLP
/
DLW
/
/
/
Abbreviation
/
/
/
/
DLR
/
CLP
/
DLW
/
CLD
/
/
Phone +39.0438.30.91.31
Need help?
Do you have a question about the AXIS HD67576-A1 and is the answer not in the manual?
Questions and answers