Channel Configuration Worksheet - Rockwell Automation AB quality Allen-Bradley 1746-INT4 User Manual

Thermocouple/mv isolated input module
Table of Contents

Advertisement

22
Quick Start
Channel Configuration
Worksheet
Channel Configuration Word (O:e.0 ... O:e.3) — Bit Descriptions
Bit or
Define
To select
Bits
0...3
Input
TC Type J
Type
TC Type K
TC Type T
TC Type E
TC Type R
TC Type S
TC Type B
TC Type N
±50 mV
±100 mV
TC Type C
TC Type D
Invalid
Invalid
Invalid
CJC Temp
Publication 1746-UM614B-EN-P - September 2007
10. Monitor the status of input channel 0 to determine its
configuration setting and operational status.
This is useful for troubleshooting when the blinking channel
LED indicates that an error has been flagged.
If the Module Status LED indicator is off, or if the Channel 0 LED
indicator is off or blinking, refer to Chapter 8.
SLC 500 Controller Data Files
Input Image
Output Image
(8 words)
Word 0
Channel 0 Data Word
Word 1
Channel 1 Data Word
Word 2
Channel 2 Data Word
Word 3
Channel 3 Data Word
Channel 0 Status Word
Channel 1 Status Word
Channel 2 Status Word
Word 7
Channel 3 Status Word
Select your bit configurations. Write them at the bottom of the
worksheet. Use one worksheet for each channel.
Set these bits in the Channel Configuration Word
15...12 11 10 9 8 7 6 5 4 3 2 1 0
In this example, during normal operation only bit 11 is set.
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
Bit 15
Address
I:1.4
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
Bit 0
Description
Project ______________
Slot Number _________
Channel Number ______
Configure the channel for the
input type connected to it. Valid
inputs are thermocouples and analog
input signals of ±50 mV and ±100 mV.
You can configure the channel to read
the cold-junction (CJC) temperature.
When reading the CJC temperature,
the channel ignores the physical input
signal.