Rockwell Automation AB quality Allen-Bradley 1746-INT4 User Manual page 32

Thermocouple/mv isolated input module
Table of Contents

Advertisement

32
Install and Wire the Module
Publication 1746-UM614B-EN-P - September 2007
Prepare and Wire the Cables
Follow these steps to prepare and connect cable leads and drain
wires.
Signal Wires
(At the module-end of the cable, extract
the drain wire but remove the foil shield.)
1. At each end of the cable, strip some casing to expose individual
wires.
2. Trim signal wires to 12.5 cm (5 in.) lengths beyond the cable
casing and strip about 4.76 mm (3/16 in.) of insulation to expose
the ends of the wires.
IMPORTANT
3. At the module-end of the cables:
– extract the drain wire and signal wires.
– remove the foil shield.
– bundle the input cables with a cable strap.
4. Connect drain wires together and solder them to a 9.5 mm
(3/8 in.) wire braid, 30.5 cm (12 in.) long, keeping drain wires
as short as possible.
5. Connect the 9.5 mm (3/8 in.) wire braid to the nearest chassis
mounting bolt.
6. Connect the signal wires of each channel to the terminal block.
Only after verifying that your connections are correct for each
IMPORTANT
channel, trim the lengths to keep them short. Avoid cutting
leads too short.
(Remove foil shield and drain wire
from sensor-end of the cable.)
Cable
Drain Wire
See the Cable Preparation and Connections to Minimize
Electrical Noise Interference illustration on page 33 for
more information about the cables.
Signal Wires

Advertisement

Table of Contents
loading

Table of Contents