Use Channel Data Words - Rockwell Automation AB quality Allen-Bradley 1746-INT4 User Manual

Thermocouple/mv isolated input module
Table of Contents

Advertisement

Use Channel Data Words

O:e.0
15
14
O:e.1
15
14
O:e.2
15
14
O:e.3
15
14
Format of a Channel Data Word
Input Type
Data Format
Engineering Units x 10
° Celsius
C
0...2317
D
0...2317
J
-210...760
K
-270...1370
T
-270...400
E
-270...1000
R
0...1768
S
0...1768
B
300...1820
N
0...1300
±50 mV
(1)
-50...50
±100 mV
(1)
-1000...1000
CJC Sensor
0...85
(1)
When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.
(2)
Type B, C, and D thermocouples cannot be represented in engineering units x 1 (°F) above 3276.7 °F. Software treats it as an over-range error.
Thermocouple or millivolt input data reside in I:e.0 to I:e.3 of the SLC
controller's input image file (where e is the slot number assigned to
the module). The values depend on the input type and data format
that you select. When an input channel is disabled, its data word is
reset (0).
SLC Controller's Input Image File (Data Word)
CH 0 Channel Data Word
13
12
11
10
9
CH 1 Channel Data Word
13
12
11
10
9
CH 2 Channel Data Word
13
12
11
10
9
CH 3 Channel Data Word
13
12
11
10
9
Engineering Units x 1
° Fahrenheit
° Celsius
32...4201
0...23,170
32...4201
0...23,170
-346...1400
-2100...7600
-454...2498
-2700...13,700
-454...752
-2700...4000
-454...1832
-2700...10,000
32...3214
0...17,680
32...3214
0...17,680
572...3308
3000...18,200
32...2372
0...13,000
(1)
-50...50
-500...500
(1)
-1000...1000
-10000...10,000
32...185
0...850
8
7
6
5
4
8
7
6
5
4
8
7
6
5
4
8
7
6
5
4
° Fahrenheit
320...32,767
320...32,767
-3460...14,000
-4540...24,980
-4540...7520
-4540...18,320
320...32,140
320...32,140
(2)
5720...32,767
320...23720
(1)
(1)
-500...500
(1)
(1)
-10000...10,000
32...1850
Publication 1746-UM614B-EN-P - September 2007
Channel Configuration, Data, and Status
3
2
1
0
3
2
1
0
3
2
1
0
3
2
1
0
Scaled-for-PID
Proportional
Counts
0...16,383
-32,768...32767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
0...16,383
-32,768...32,767
51