Rockwell Automation AB quality Allen-Bradley 1746-INT4 User Manual page 19

Thermocouple/mv isolated input module
Table of Contents

Advertisement

3. Install the module.
Make sure system power is off; then insert the module into the
I/O chassis. In this example procedure, the module is inserted
into slot 1.
4. Connect thermocouple wires to channel 0 on the module's
terminal block.
Make sure both cold-junction compensation (CJC) devices are
securely attached.
Terminal Block
CJC A
Device
5. Configure the software to accept the module.
Type the module's ID and assigned slot (slot 1 in this example)
into the system I/O configuration.
Top and Bottom
Module Releases
Card
Guide
CHL 0+
Important:
Ground the thermocouple's cable shield
CHL 0-
to the I/O chassis with 9.5 mm (3/8 in.)
braid wire. (Refer to page 31.)
CHL 1+
CHL 1-
Thermocouple
Wire
Publication 1746-UM614B-EN-P - September 2007
Quick Start
19