Download Print this page

Gardner Denver ELECTRA-SAVER II Service Manual page 39

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

160"
F. This system
provides
proper
compressor
warm-up
and
prevents
moisture
contamination
of the oil
(screening)
to remove
debris
sand andlor
silt in the cooling
water
suPPlY.
However
chemical
treatment
methods
may
be necessary
in certain
instances
to inhibit
corrosion
and/
or remove
suspended
solids to alter the water's
tendency
to
form scale
deposits
or prevent
growth
of microorganisms
The
normal
maintenance
program
for the
unit should
in-
clude
periodic
cleaning
on the tube side (water
side) of the
heat exchanger
to remove
deposits
which
enhance
fouling
and corrosion.
WATER
FLOW
CONTROL
VALVE
FOR
HEAT
EX-
CHANGER
(Optional
Equipment
Recommended
To
Conserve
Water
Where
Appropriate)
( Figures
1-5,
7-5
& 8-5) –
The water
flow control
valve is adjustable
to comp-
ensate
for varying
water
inlet temperatures
and pressures
Use the compressor
discharge
air temperature
gauge
on
the instrument
panel
in setting
the flow control
valve
The
compressor
discharge
temperature
must be maintained
a
minimum
of 10°
F. above
the dew point temperature
at the
maximum
anticipated
ambient
refer
to Figure
8-5
for the
To check
element
heat in oil — it should
be fully extended
at 160°
F. If unit shuts
down
due
to high
air discharge
temperature
the cause
may be that the element
is stuck
open to the bypass
in which case lines 1 and 2 (Figure
1-5)
will be hot to the touch and lines3
and4
much cooler. When
flushing
the oil system
remove
mixing
valve and clean
all
parts
thoroughly.
OIL
IN
FROM
COOLER
OIL IN
FROM
RESERVOIR
CAPILLARY
TUBE
Y
676347
OIL TO
COMPRESSOR
ADJUSTING
SCREW
\
.
SETTING ~
"
SCALE
FIGURE
6-5.
THERMAL
CONTROL
(THERMOSTATIC
MIXING)
VALVE
COMPRESSOR
OIL
COOLER
WATER-COOLED
HEAT
EXCHANGER
(Figure
3-1 ) –
The
heat
exchanger
oil cooler
is a multiple
pass type,
with water
in the tubes
and oil in the shell.
The oil temperature
is controlled
by
the thermal
control (thermostatic
mixing) valve. The optional
water
control
valve
may be used
to conserve
water.
VAL
A74099A
HEAT
SENSING
BULB
/
Oil cooler
malfunction
may
be traced
by checking
pres
sure
at oil inlet
and
outlet
Fitting
in the
oil
cooler
at
these
locations
are equipped
with a pipe tap for a gauge.
At normal
operating
air service
pressure
(65 to 150
PSIG)
with
unit
warm
a pressure-drop
of 2 to 25
PSI
can
be
expected
between
the oil inlet
and the oil outlet
FIG
IRE 7-5.
WATER
CONTROL
VALVE
2UI
220
m
180
I@
la
lm
lW
M
m
a
Water
pressure
drop
from
water
inlet
to outlet
will vary
with
the
inlet
pressure
and
amount
of water
flowing
A
normal
pressure
drop
may
range
from 5 to 10
PSI.
Any
change
in the pressure
drop from that normally
held may
indicate
tube leakage
or fouling
and should be investigated
In many
instances
the cooling
water
supply
for the
heat
exchanger
will contain
impurities
dissolved
in solution
and/
or in suspension
These
substances
can cause scale forma
tions
corrosion
and fouling
(plugging)
of any water-cooled
heat
exchanger
equipment
Disregarding
the
possibility
that
one
or more
of these
conditions
exists
may
result
in increased
maintenance
and operation
expense
reduced
equipment
life
and
emergency
shutdown.
It is strongly
recommended
that a reputable
local water
treatment
con
tern
be engaged
to establish
the corrosion
Scale-forming
and fouling
tendency
of the cooling
water
and take
steps
necessary
to remedy
the situation
if a problem
does exist
The
need
for water
treatment
may only
involve
filtration
m
40
m
.80
100
120
MWENT
TW.
-
*F
FIGURE
8-5.
DEW
POINT
TEMPERATURE
VS
AMBlENT
TEMPERATURE
(100%
RELATIVE
humidity
13-9-630
Section
5
Page
5

Advertisement

loading

This manual is also suitable for:

EcqqnEcqsnEcqqoEcqso