Download Print this page

Gardner Denver ELECTRA-SAVER II Service Manual page 18

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

two-probe
high
discharge
temperature
switch
have
an
indicating
pilot light mounted
in the control
box door.
The
amber
lighted
ON
indicates
compressor
running
under
Constant
Speed
Control
Under
Automatic
Start/Timed
stop
the compressor
may be stopped
with the amber
light
ON indicating
power
on
The blue lighted
LOAD
indicates
compressor
is loaded
To replace
the
bulbs
in the
pilot
light (replacement
bulb
number
is Sylvania
120
PSB
or equal
1.
Turn
power
off at main
breaker
panel
2.
Open
control
panel
3.
Turn
slotted
locking
screw
on upper
side
of pilot
light
body
counterclockwise
1/4
turn
and
remove
the
body from the
lens
holder.
4.
Remove
old
bulb
located
in the
body
and
insert
new
bulb
5.
Reassemble
body to lens holder
and secure
by turn-
ing locking
screw
1/4
turn
clockwise
ON-OFF
SWITCH
(Figure
2-1)
Early
model
Constant
Speed
units with Low Demand
Mode
switch
and the units
with Automatic
Start/Timed
Stop
with Low Demand
Mode
have an ON-OFF
push button with an amber
lighted
section
to indicate
ON (compressor
running)
and a green
lighted
section
to indicate
LOAD
(compressor
loaded).
The
red
bar on the
bottom
of the ON-OFF
switch
is the OFF
and
RESET
on the
Constant
Speed
unit
with
Low
Demand
Mode
The black bar on the bottom
of the Automatic
Start/
Timed
Stop
ON-OFF
switch
is the
RESET.
To replace
the bulb (Sylvania
120
PSB
or equal
in any of
the switches
1.
Turn
the
power
off at the
main
breaker
panel
2.
Open
the control
panel.
3.
Turn the slotted
locking
screw
on the upper
side of
the
switch
body
counterclockwise
1/4
turn
and
re
move
the
switch
body
from
the
switch
operator.
4.
Remove
the old bulb located
in the stem of the switch
body
and
insert
the
new
bulb
5.
Reassemble
the switch
body to the operator
and lock
in place
by turning
the locking
screw
1/4
turn clock-
wise.
LOW
DEMAND
MODE
SWITCH
(Figure
2-1)
The
low demand
mode
switch
when
turned
to the
ON
POSi
tion
will
blow
the
reservoir
down
when
the compressor
unloads
When
switch
is turned
to OFF,
unit will retain
pressure
in reservoir
when
unloaded
~WARNING
The low demand mode switch CANNOT
be used with
remote elevated oil coolers
These units require special
wiring
diagrams
— check with factory.
SAFETY
DEVICES
these
safety
device%
Both
control
systems
incorporate
Motor
Protection
Devices
— Overload
heaters
are
fur-
nished
for the
air-cooled
oil cooler
fan
motor
starter
in
the voltage
range
specified
There
are three
(3) overloads
of proper
size for the starter
and its enclosure.
When
re
placing
or changing
overloads
be sure to select
them from
a 3-overload
heater
table
since the use of a third overload
derates
each
overload
for a given
enclosure
due
to the
extra
heat
An overload
from
a 2-overload
heater
table
would
be undersize
The
overload
heaters
are
in a common
overload
block
in
the starter
and have a single
common
percentage
adjust-
ment knob with a 90 to 1 10% range.
The knob is set at the
factory
on the
100%
mark
Main
unit starter
should
be adequately
fused
and provided
with overload
heaters
suitable
for the application
to pro
vide
protection
for the
unit drive
motor.
High
Discharge
Temperature
Switch
— Later
Models
— Later
models
of the compressor
unit are protected
from
high
discharge
temperature
by a two-probe
adjustable
switch.
One probe
is located
in the discharge
pipe between
the compressor
and the oil reservoir
to sense
compressor
discharge
air/oil
mixture
temperature.
The second
probe
is located
in the final
discharge
manifold
and senses
the
temperature
of the air at the oil separators
The switch
is
located
inside
the control
box (Figure
2-l);
the shutdown
temperature
is set on the adjustable
dial
If the temper-
ature
of the air at either
of the probes
exceeds
the tem-
perature
set on the dial
the switch will stop the unit
Press
reset button
of the Start/ Stop(On-Off)
switch
then the Start
(On)
button
to restart
the
unit
CAuTION
This adjustable
switch
dial
must
not be set higher
than
225°
F.
DO not continue
to reset the circuit if the same mal-
function
occurs within
a short period of time
Find
and
correct
the
trouble
before resuming
operation
In addition
to protecting
the
unit from
damage
or failure
resulting
from
high
air temperature,
the
switch
also
in
corporate
four (4) indicator
lights
which
show
the
point
of high temperature
and/or
the condition
of the tempera
ture probes
This information
is shown
on the decal
inside
the control
box and
in Figure
2-4.
The High Air Temperature
Switch
may be checked
period
ically
to assure
proper
operation
To check
with the unit
running
turn the dial on the switch
to the temperature
in-
dicated
by the discharge
temperature
gauge.
Unit should
shutdown
If it doea
not
check
the
temperature
gauge
accuracy
and indicator
lights—
refer to the condition
decal
on the control
box door for the malfunction
After
opera-
tional
check
always
reset
switch
dial to the proper
setting
(225°
F.).
Automatic
Blowdown
Valve
A pilot-operated
valve
piped
into the oil reservoir
final discharge
manifold
ahead
of the check
valve and connected
to the unloader
solenoid
valve
which
is wired
into
the
motor
control
circuit
will
release
pressure
from the oil reservoir
each time the unit is
unloaded
with low demand
mode switch
ON or when
unit is
shut down. The blowdown
line is equipped
with a muffler
to
reduce
air discharge
noise.
13-9-630
Section
4
Page
2

Advertisement

loading

This manual is also suitable for:

EcqqnEcqsnEcqqoEcqso