Download Print this page

Gardner Denver ELECTRA-SAVER II Service Manual page 23

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

will blow down
If the system
pressure
does
not fall to the
pressure
switch
low setting
within the time set on the timer,
the
unit will stop
The ON indicator
light will remain
on as long as the On-Off
switch
ON
pushbutton
is depressed
When
air
is again
required
the
unit will start
the
timer
will reset
and
the
loaded
unloaded
stop
cycle
will repeat
The timer must never be set at a time less than that indicated
by
the minimum
run time caution plate on the instrument
panel
Use of less time of run interval
will allow
excessive
motor
starts
and
cause
shortened
motor
life or failure
When
the low demand
mode
switch
is in the ON position
and
timer
is positioned
so the
letter
"N'
in MINUTE
is
opposite
the
green
arrow
mark
on the
escutcheon
the
compressor
will
build
to full
pressure
unload
and
blow
down
At this setting
the motor will not time
out and stop
ing the compressor
to load
up and
operate
normally.
The control
consists
of a flow controlcheck
valve,
a small
surge
changer,
a normally
open
three-way
air valve,
and a
shuttle
valve.
The Flow
Control-Check
Valve
consists
of a check
valve
and an adjustable
orifice
in one
body
see
Figure
8-4.
The
Three-Wey
Valve
(Figure
9-4)
requires
15
PSIG
control
pressure
to shift
the valve
L
.-—
-.J
>
ADJUSTABLE
CONTROLLED
FLOW
FREE
FLOW
THRU
CHECK
VALVE
MINIMUM
RUN
TIME
SETTING
FOR AUTOMATIC
START/TIMED
STOP
CONTROL
Size
Time (Minutes)
All
6
Electrical
Wiring
— Figures
16-4
and 17-4
are the wiring
diagrams
for the
units
with
Automatic
Start/Timed
Stop
Control
System
VIBRATION
SWITCH
(Optional
Equipment)
— The
op
tional
vibration
shutdown
switch,
mounted
on the
com-
pressor
coupling
cover, detects
an increase
in vibration
that
could be an indication
of impending
damage
to the unit The
switch
actuates
when
the
selected
level
of vibration
is
exceeded
The
switch
MUST
BE ADJUSTED
when
the
unit
is first
installed.
Refer to switch
manufacturer's
instruction
manual
for complete
details
AUXILIARY
AIR RECEIVER—
An auxiliary
air receiver
with
adequate
volume
must be used with both control
systems
to prevent
rapid
cycling
of the unit
Occasionally
shop air
lines are of such a length as to provide
adequate
volume
but this should
be carefully
checked
before
using the unit
without
an auxiliary
air receiver.
LOW
STARTING
TORQUE
(Unloaded
Start) CONTROL
(Optional
Equipment)
— When
a reduced
voltage
closed
transition
starter
is used
problems
may arise as the torque
required
by the compressor
may exceed
that available
from
the
compressor
drive
motor
during
and
just
after
the
starting
cycle
This is especially
true when
a unit uses full
motor horsepower
at some
pressure
lower than 100
PSIG.
The
Low
Starting
Torque
Controls
holds
the compressor
inlet
valve
closed
for a short
period
while
the
motor
is
starting
and reduces
internal
air loads and the compressor
torque
The control
allows
the compressor
to build up a pressure
of
approximately
15 PSIG
in the oil reservoir
which is directed
to the pilot on the inlet valve to close
the valve and unload
the compressor
while the motor
reaches
full load speed
A
pneumatic
timing
circuit
then
bleeds
the pressure
off the
inlet valve
pilot after
approximately
10-15
seconds
allow
FIGURE
8-4
— FLOW
CONTROUCHECK
VALVE
3
0-15
pSIG
15 PSIG
DE-ENERGIZED
ENERGIZED
FIGURE
9-4
THREE-WAY
VALVE
CAuTiON
This control will function
properly only when the
low
Demand
switch if OFF If the Low Demand
switch is
ON
the Low Torque control will react to all demands
for air as initial
start-up
and delay buildup
in air
pressure for the time delay built into the system
In operation
(Figure
10-4),
the adjustable
orifice
in the flow
control
check
valve controls
the rate at which
pressure
will
build
in the surge
chamber
the unloaded
starting
time
is
proportional
to
the
pressure
buildup
time
When
the
pressure
in the surge chamber
reaches
15 PSIG, the three
way valve
will shift
bleed
control
pressure
from the
inlet
valve
and purge
valve,
and allow
the compressor
to load
See
Figure
10-4
for the
complete
Low
Starting
Torque
Control
assembly.
Figure
11-4
is the
unit tubing
diagram
with
control
in place
RESERVOIR
PRESSURE
SWITCH
The
reservoir
pres-
sure switch
will prevent
motor damage
if an attempt
to start
motor
is made
before
the
reservoir
is completely
blown
down
The
pressure
switch
will not allow
the motor
to be
restarted
after
the unit has stopped
until the pressure
in
the
reservoir
is below
5
PSIG.
The
switch
pressure
is
sensed
at the separator
tower
section
of the oil reservoir.
The switch
is factory
set at 5 PSIG, with an adjustable
range
of 3-30
PSIG.
, WARNING
Do not set pressure switch to pressure
above 5 PSI.
13-9-630
Section
4
Page
7

Advertisement

loading

This manual is also suitable for:

EcqqnEcqsnEcqqoEcqso