Download Print this page

Gardner Denver ELECTRA-SAVER II Service Manual page 38

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

OIL
'OUT
WHITE
R
INDIcATOR
SHOWS
NORMAL
OPERATION
FIGURE
5-5.
INDICATOR
SHOWS
"CHANGE
FILTER"
675792
CONDITION
COMPRESSOR
OIL
FILTER
free
compressor,
since
it removes
dirt and abrasives
from
the circulated
oil
The filter
is equipped
with a relief
valve
that opens
in the event
the element
becomes
dirty enough
to block
the flow of oil
~CAUTION
Element
must be replaced every 1000 hours or sooner
or when top of the indicator
on the filter
is in red
"Change Filter" half of window.
Unit must be run-
ning and warmed up for indicator
to read accurately.
Check with light to be certain of indicator
position
.
some lubricants
will obscure the indicator
Use only the replacement
element
shown
on the filter tag
or refer
to the
parts
list for the
part
number.
Use
the
following
procedure
to replace
the filter
element
Do not
disturb
the
piping
.
1.
DANGER
Stop unit and be
reservoir
2.
3.
sure no air pressure
is in the oil
To remove
cannister
(3) rotate
tie bolt (1 O) counter-
clockwise
until cannister
is free of head assembly(l).
Remove
the element
(6) from cannister.
Remove
in-
dicator
assembly
(5)
from
the
element
by inserting
screwdriver
between
indicator
assembly
and element
and carefully
prying downward
Inspect
0-ring
(4) for
cuts
or excessive
wear
and
discard
the
element
Rinse
out cannister
with
clean
fluid
to remove
any
contamination
Remove
O-ring
(2) from head
assembly
and inspect
for cuts or excessive
wear.
Wipe O-ring
area of head
(1) with clean
cloth and after covering
O-ring with oil
reinstall
in head
assembly.
Check
the indicator
as
sembly
(5)
machined
bore
in the
head
for burrs
or
deep
scratches
and carefully
smooth
out if required
4.
5.
6.
Install
indicator
assembly(5)
into new element
Place
the
element
into
cannister
making
sure
spring
(8),
washer
gasket
(9) and tie bolt (1 O) are in the proper
position
NOTE
Large diameter
end of spring should contact the new
element
Place
cannister
as previously
assembled
into head
assembly
and
rotate
bolt clockwise
until torqued
to
20
foot-pounds
If leakage
appears
at bottom
of cannister,
replace
washer
gasket
(9).
If leakage
appears
at top of can
nister
replace
O-ring
(2).
If this does
not stop the
leakage,
the cannister
may be nicked
or distorted
by
overtorquing
and should
be replaced
COMPRESSOR
OIL
COOLER
( RADIATOR
TYPE)
MODULE
— The
air-cooled
oil cooler
module
is remote
mounted
The oil cooler
requires
pipe and electrical
connection
to the
main compressor
unit
Connecting
piping
and wiring
are
furnished
by the
user.
See " Installation"
Section
2.
Do not obstruct
the
air flow
to and
from
the
oil cooler.
Allow
two (2) feet
clearance
on all sides
of the oil cooler.
See Figure 2-2 for cooling
air flow requirements
Keep both
faces
of the oil cooler
core clean for efficient
cooling
of the
compressor
oil
Oil cooler
malfunctions
may be traced
by
checking
oil pressure
drop through
the oil cooler
check
by
installing
pressure
gauges
at fittings
in the inlet and outlet
oil piping
near the end of the cooler.
At normal
operating
air service
pressures
(65
to 150
PSIG)
with the unit warm
a pressure
drop of 2 to 25 PSIG
can be expected
between
the inlet and outlet side of the cooler.
The instrument
panel
thermometer
indicates
compressor
discharge
air temper-
ature which would also be the approximate
oil temperature
into the
mixing
valve
An oil filler
stand
pipe
and
plug
must
be located
in the
piping
on the oil cooler
module
for ease
of filling
the oil
cooler
when
it is mounted
at a distance
from
the
com
pressor
unit
When
filling a remotely
mounted
oil cooler
be sure all lines
to and from the compressor
unit are also filled
to prevent
excessive
drawdown
of the oil supply
in the oil reservoir.
A vent line should
be installed
between
the oil cooler
and
compressor
oil reservoir
as an aid in filling
and to prevent
siphoning
THERMAL
CONTROL
(THERMOSTATIC
MIXING)
VALVE
(Figure
6-5)
on current
units is installed
in system
as shown
in Figure
1-5 (on early
units this valve
is in line
between
reservoir
and cooler.
This valve is used to control
temperature
of the oil in both
radiator
and tube
type
oil
cooler
systems
The element
is so designed
that a portion
of the oil can flow through
the oil cooler
at all times
On
start- up with unit cold
element
is open to bypass
allowing
oil to pass directly
from the reservoir
to compressor
during
warm-up.
As oil warms
element
gradually
closes
to the
bypass
allowing
more of the oil from the cooler
to mix with
oil from the bypass
After
unit is warmed
up mixing
valve
maintains
oil injected
into
compressor
at a minimum
of
13-9-630
Section
5
Page
4

Advertisement

loading

This manual is also suitable for:

EcqqnEcqsnEcqqoEcqso