Download Print this page

Gardner Denver ELECTRA-SAVER II Service Manual page 11

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

only, as standard
equipment
The enclosure
reduces
the
normal
operating
sound
of the
unit to 90
DBA
or below
in free
field
conditions
AIR-COOLED
OIL
COOLER
MODULE
The
air-
cooled
oil cooler
is a separate
module
and may be mounted
remote
to the compressor
unit
Ventilation
— The oil cooler
requires
adequate
cooling
air
flow.
Proper
ventilation
MUST
be provided
with
hot air
exhausted
away
from the cooler
take
care
that hot air is
not recirculated
from the exhaust
to the inlet side
of the
cooler.
Cooling
air flow direction
is from
the motor
side
through
the grille
side
of the oil cooler.
Do not obstruct
the
air
flow
to
or from
the
cooler.
Allow
two (2)
feet
clearance
on all sides of the cooler
module
See Figure 2-2
for cooling
air flow
requirements
Low
Oil
Pressure
Protection
— The
standard
factory
installed
low oil pressure
shutdown
switch
in the control
box will prevent
start-up
or shut the unit down
if oil pres
sure
is not established
or maintained
due to malfunction
in the
oil cooler
system
Oil
Cooler
— The
oil cooler
module
can
be mounted
in
any
of several
remote
locations
close
coupled
but not
joined
to the compressor
unit
horizontal
remote,
located
on the same
level
as the compressor
unit
but some
dis
tance
away
or overhead
remote
located
above
level of the
compressor
unit
as on a roof.
~WARNING
The low demand mode switch CANNOT
be used with
remote overhead oil cooler
These units require special
wiring
diagram — check with factory.
All piping
and wiring
between
the compressor
unit and the
remote
oil cooler
is to be supplied
by the
user.
THE
DESIGN
OF
THE
REMOTE
OIL
COOLER
MODULE
SYSTEM
MUST
BE
APPROVED
BY
THE
FACTORY
BEFORE
INSTALLATION.
The
design
information
to be
submitted
for approval
includes
1.
Location
of oil cooler
module
— inside
or outdoors
2.
Range
of operating
ambient
temperatures
at the oil
cooler
location
3.
Elevation
of the oil cooler
above
the compressor
unit
4.
Pipe type and size(s)
to be used to connect
oil cooler
and compressor
unit
Minimum
pipe size
is 2" IPS
5.
Horizontal
and
vertical
lengths
of the
pipe
run
If
more
than
one pipe size
is used
list length
of each
size
and total
length.
6.
Number
and size
of elbows
tee%
unions
reducers
and valves
to be used
in the
pipe
run
7.
A dimensioned
sketch
of the proposed
piping system
showing
location
of the compressor
unit
oil cooler
and
pipe
fittings
of 3 through
6 above
All remote
piping
should
be of adequate
size to insure
the
minimum
pressure
loss
Design
point4
above
lists the pipe
size at the compressor
unit oil inlet and outlet
connections
and is the minimum
pipe size to be used
Long runs of pipe
and the use of valves
and fittings
require
larger
than the
minimum
pipe
sizes
in the
system
to keep
the
pressure
loss low.
All pipe and fittings
used
in a remote
oil cooler
system
should
be galvanized
or treated
internally
to pre
vent
rust
and
all valves
are
to be of a nonferrous
con
struction
to prevent
corrosion
and fouling
The remote
cooler
should
be placed
so that the fan air flow
through
the
cooler
(air
flow
is from
motor
side
through
core)
and the
prevailing
winds
are
in the same
direction
A baffle
should
be provided
on the
exhaust
side
of the
cooler
for protection
against
occasional
wind
shifts
When
the oil cooler
is mounted
above
the compressor
unit
a check
valve
is to be mounted
on the compressor
unit
in
the line to the oil cooler
see Figure 2-5.
A pneumatic
pilot-
operated
normal-closed
valve
is to be mounted
at the
oil filter
inlet
on the
compressor
unit
line
from
the
oil
cooler
see Figure
2-5.
The check
valve
permits
oil flow to
the
oil cooler
during
operation,
but
prevents
return
oil
flow from the cooler
when
the unit is shut down
The pilot
valve is held open by air pressure
from the unit oil reservoir
during
operation
and
closes
under
spring
load when
the
unit is shut
down
to prevent
return
oil flow
from
the oil
cooler.
An oil filler
stand
pipe
and
plug
must
be located
in the
piping
on the
oil cooler
module
for ease
of filling
of a
remote
oil cooler
see
Figure
2-5.
INSTALLATION
FOR
COLD
WEATHER
OPERATION
— It is recommended
that whenever
possible
the unit be
installed
inside a shelter
that will be heated
to temperatures
above
freezing
(32"
F., 0° C.).
This will eliminate
many
of
the problems
associated
with operating
the units outside
in cold climates
where
freezing
rain, drifting
snow, freezing
condensate
and bitter
cold temperatures
are encountered
When
an outside
installation
must
be made
the
precau-
tions required
will depend
on how severe
the environment
will get
The following
are general
guidelines
for outside
installations
Cold
Weather
(Down
To –10°
F.)
1.
2.
3.
4.
5.
6.
13-9-630
Section
2
Be sure all control
Iines
drains
and traps
are heated
to avoid freezing
of condensate
Heat tape with ther-
mostat
control
is generally
satisfactory
for this pur-
pose.
This is not a factory
option
but can be obtained
at various
local
plumbing
or hardware
outlets
If an air-cooled
aftercooler
is to be used
provisions
to
bypass
the aftercooler
should
be made
Since cold air
contains
very little moisture
successful
operation
can
be
achieved
without
the
aftercooler.
Successful
operation
down
to +15°
F. can be accomplished
by
reversing
fan flow, but cooler
bypass
should
still be
provided
should
it be required
Provide
at least
some
simple
shelter
(Plywood
wind
break
etc)
to protect
against
drifting
snow.
Use
only
Gardner- Denver
"GD800
Lubricating
Coolant'.
Monitor
unit carefully
during
start-up
and operation
to be sure
it is functioning
normally.
When
the
coolers
are
mounted
horizontally
use
weather
protected
enclosure
for the
unit
Page
2

Advertisement

loading

This manual is also suitable for:

EcqqnEcqsnEcqqoEcqso