Gardner Denver ELECTRA-SAVER II Service Manual page 14

Stationary base mounted compressor
Hide thumbs Also See for ELECTRA-SAVER II:

Advertisement

of 3 through
5 above
Water
Cooled
Machines
(Figure
4-2)
— On water-cooled
machines
with aftercooler,
the moisture
separator
and con
densate
drain
are shipped
loose
and must be installed
by
customer.
Customer
must
furnish
and
install
all water
piping
required
CONTROL
PIPING
Control
piping
is not
necessary
since
the
Electra-Saver
II
unit is factory
wired
and piped
for the control
system
specified
INLET
LINE
— Where
an inlet
line
is used
between
an
outside
air filter
and the
compressor,
or to connect
the
unit mounted
air filter
to an outside
source
of air, it must
be thoroughly
cleaned
on the
inside
to prevent
dirt
or
scale
from entering
the compressor.
If welded
construc-
tion
is used,
the line
must
be shot
blasted
and cleaned
to remove
welding
scale.
In either
case
the inlet
line
must be coated
internally
by galvanizing
or painting
with a
moisture
and
oil proof
sealing
lacquer.
The
inlet
line
should
be the full size
of the
inlet
opening
on the com-
pressor.
If an extra-long
line
is necessary,
the pipe
size
should
be increased
accordingly
Length
Of Inlet
Line
Diameter
Of Pipe
Size
0 to 10
Ft . . . . . . . Same
As Compressor
Inlet
Opening
10
to 17
Ft
. .
One
Size
Larger
Than
Inlet
Opening
17
to 38
Ft
. . . . . Two Sizes
Larger
Than
Inlet
Opening
Accessibility
for inlet
air filter
servicing
must
be consid
ered
when
relocating
the filters
from the unit to a remote
location
DISCHARGE
SERVICE
LINE
The
discharge
service
line connection
on water-cooled
units
with aftercooler
is
made
at the moisture
separator.
On air-cooled
units and
water-cooled
without
aftercooler,
the connection
is made at
the minimum
pressure
valve located
behind
the instrument
panel
When
manifolding
two or more
Electra-Saver
II
units
on the same
Iine
each unit is isolated
by the check
valve in
the unit discharge
line
If an
Electra-Saver
II
unit is mani
folded
to another
compressor,
be sure the other compres
sor has a check
valve in the line between
the machine
and
the
manifold
If an
Electra-Saver
II
and
a reciprocating
compressor
are manifolded
together,
an air receiver
must
be located
between
the two
units
DANGER
DO
NOT
USE THE AIR DISCHARGED
FROM
THIS
UNIT
FOR
BREA THING
— IT IS NOT
SUITABLE
FOR HUMAN
CONSUMPTION.
BLOWDOWN
VALVE
PIPING
The
biowdown
valve
is fitted
with
a muffler,
for operation
indoors
If the
in
stallation
requires
the
muffler
may
be removed
and
the
biowdown
valve
piped
to the outside
with
pipe the same
size
as the
blowdown
valve
outlet
connection
WATER
PIPING
(Watercooled
Heat
Exchanger
Models
Onlyj
On machines
equipped
with a water-cooled
heat
exchanger,
pipe
water
to the
inlet
or water
flow
control
valve
mounted
in the
water
inlet
piping
to the
heat
ex-
changer.
Pipe
outlet
water
from
the
outlet
or magnetic
water
shutoff
valve
to a sump
or drain
The thermal
bulb
is inserted
in the
heat
exchanger
oil outlet
line
refer
to
the
unit outline
drawing
for location
The
water
source
should
be capable
of supplying
up to
the maximum
flow shown
in Figure
5-2 at a minimum
pres
sure
of 40
PSIG
maximum
allowable
water
pressure
is
150
PSIG
The water
flow rates
shown
in Figure
5-2
are
approximate
and
a guide
to sizing
piping
cooling
tower
and other
water
system
equipment
The heat exchanger
is designed
to operate
with water
inlet
temperatures
from
60°
F. to 90°
F., and
a water
outlet
temperature
not to exceed
110°
F.
If water
cooler
than
60°
F. is used
high water
outlet temperatures
(overl
10° F.)
will be experienced
along
with shortened
heat
exchanger
life caused
by tube fouling
and corrosion
If water
warmer
than 90°
F. is used
higher
compressor
oil temperatures
and
high water
usage
will result
Most
water
systems
will
require
control
of
impurities
filtration,
softening
or other
treatment
See
"Compressor
Oil
Cooler
Water-Cooled
Heat
Exchanger"
for
more
information
on the water
system.
Aftercooler
— Heat
Exchanger
Water
Piping
(Figure4-2)
— If an aftercooler
is used
and
piped
in series
with
the
heat
exchanger,
install
the
water
flow
control
valve
and
magnetic
water
shutoff
valve,
if used
downstream
of the
exchanger.
PiPe
the aftercooler
water
outlet
to the heat
exchanger
water
inlet
on the compressor
unit
If the
aftercooler
is piped
in parallel
with
the
heat
ex-
changer,
provide
a manual
valve
between
the aftercooler
outlet
and the heat exchanger
outlet
after the water
control
valve to adjust
aftercooler
water
flow for discharge
temper-
ature
required
and
most
economical
water
use
separate
water
inlet
lines
are
piped
to the
aftercooler
and
heat
exchanger.
~CAUTION
When an ajtercooler
is piped
in series with
the oil
cooler the maximum allowable waterflow
rate through
the oil/aftercooler
system
is the maximum
allowed
by the aftercooler.
If the oil cooler requires
more
water flow
than the maximum
allowed
by the after-
cooler
a parallel
water piping
system must be used
If the
standard
factory
built-in
aftercooler
is used
the
maximum
allowable
water
flow through
the aftercooler
is
30
gallons
per minute
and the maximum
water
inlet pres
sure is 150
PSIG.
If another
aftercooler
is used
consult
the
manufacturer
for operating
limits
The
water
control
valve
MUST
be used
to maintain
dis
charge
temperatures
approximately
10
F* over
the
dew
point for expected
ambient
(Figure
8-5).
See Section
5 for
adjustment
instructions
and
maximum
allowable
oil tent
perature
ELECTRICAL
WIRING
The
Electra-Saver
II
unit
is
furnished
with
the compressor
motor
enclosure
as spec
ified
by the user.
If the unit has an air-cooled
oil cooler,
this fan motor
is a totally
enclosed
"air-over"
or fan-cooled
type
and is complete
with starter
and enclosure
as spec
ified by the user.
Allow 42"
deep
by 30"
wide clear
space
to nearest
obstruction
over
control
enclosure
in accord
ante
with Article
110-16
(a) National
Electrical
Code
it is necessary
to connect
the
compressor
unit (and
oil
cooler,
if used)
to a main starter
of the correct
size
power
characteristics
and
enclosure
for
the
application
See
13-9-630
Section
2