Burkert 8694 REV.2 Operating Instructions Manual page 54

Positioner top control basic
Hide thumbs Also See for 8694 REV.2:
Table of Contents

Advertisement

Figure 38:
Connection of screw-type terminals
Connect the positioner according to the following tables:
Input signals from the control centre (e.g. PLC)
Terminal Configuration
4
Set-point value +
5
Set-point value GND
1
Digital input +
Table 23:
Assignment of screw-type terminals, input signals of the control center, cable gland
Connection type 3-wire or 4-wire (setting via communication software):
Connection type 4-wire (factory setting)
The set-point value input is designed as a differ-
ential input, i.e. the GND lines of the set-point value
input and the supply voltage are not identical.
Note: If the GND signals of the set-point value input
and the supply voltage are connected, the 3-wire
connection type must be set in the software.
+
4
5
I
7
+
U
6
Table 24:
Connection type
54
0/4-20 mA
GND
+24 V DC
english
Type 8694 REV.2
Electrical installation 24 V DC
1
2*
3*
4
5
6
7
* Only for variant with
analog output
External circuit
4
+ (0/4 – 20 mA)
5
GND
see table "Connection type
3-wire or 4-wire"
1
+
with reference to terminal 7 (GND)
Connection type 3-wire
The set-point value input is related to the GND line
of the supply voltage, i.e. setpoint input and supply
voltage have a common GND line.
+
4
0/4-20 mA
I
GND
7
+24 V DC
+
U
6
0 – 5 V
(logical 0)
10 – 30 V (logical 1)