7.3

Configuration of the buttons

To operate the DIP switches and buttons, make sure that the local control lock is deactivated/
unlocked (factory setting): with communication software or fieldbus communication.
The configuration of the 2 buttons varies depending on the operating state (AUTOMATIC / MANUAL).
The description of the operating states (AUTOMATIC / MANUAL) can be found in the chapter entitled "7.1
Operating state".
Figure 12:
Description of the buttons
ATTENTION!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the body casing or transparent cap, do not hold the actuator of the
process valve but the basic housing.
To operate the buttons, unscrew the transparent cap
Figure 13:
Open positioner
MANUAL operating state (DIP switch 4 set to ON):
Button
Function
Aerate
1
(manually open / close the actuator)
Deaerate
2
(manually open / close the actuator)
1 and 2
Longer than 10 s (< 30 s, LED 2 flashes at 5 Hz): Device restart
simultane-
Longer than 30 s (LED 2 flashes at 10 Hz): Reset device to factory setting
ously
Table 7:
Configuration of the buttons for MANUAL operating state
13) Depending on the operating principle of the actuator.
28
Button 1
Transparent cap
Body casing
Basic housing
Actuator
english
Type 8694 REV.2
Control and display elements
Button 2
13)
13)